VIII
Test Run Mode ]
- 129 -
HWE10130
GB
Operation
Outdoor unit model
PUHY-RP500YSJM-B
PUHY-RP250YJM-B
PUHY-RP250YJM-B
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
27°C/19°C
[81°F/66°F]
Outdoor
35°C/- [95°F/- ]
Indoor
unit
No. of connected
units
Unit
4
No. of units in opera-
tion
4
Model
-
250/125/100/32
Piping
Main pipe
m [ ft ]
10 [32-3/4]
Branch pipe
5 [16-3/8]
Total pipe length
30 [98]
Fan speed
-
Hi
Amount of refrigerant
kg
[ lbs-oz ]
26.1 [58]
Outdoor
unit
Electric current
A
29.0
Voltage
V
400
Compressor frequency
Hz
62
62
LEV open-
ing
Indoor unit
Pulse
349/345/293/235
SC (LEV1)
287
287
LEV2
1400
1400
Pressure
High pressure (after O/S)/low
pressure (before accumulator)
MPa
[ psi ]
2.78/0.86
2.78/0.86
[403/125]
[403/125]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C [ °F ]
76 [169]
76 [169]
Heat exchanger out-
let (TH3)
45 [113]
45 [113]
Accumulator inlet
16 [61]
16 [61]
Accumulator outlet
16 [61]
16 [61]
SCC outlet (TH6)
29 [84]
29 [84]
Compressor inlet
16 [61]
16 [61]
Compressor shell
bottom
35 [95]
35 [95]
Indoor
unit
LEV inlet
10 [50]
10 [50]
Heat exchanger
outlet
12 [54]
12 [54]
Summary of Contents for PUHY-RP200
Page 9: ...HWE10130 GB ...
Page 11: ... 2 ...
Page 21: ... 12 I Read Before Servicing GB HWE10130 ...
Page 23: ... 14 ...
Page 63: ... 54 II Restrictions GB HWE10130 ...
Page 65: ... 56 ...
Page 75: ... 66 ...
Page 83: ... 74 IV Remote Controller GB HWE10130 ...
Page 85: ... 76 ...
Page 89: ... 80 ...
Page 95: ... VI Refrigerant Circuit 86 HWE10130 GB ...
Page 97: ... 88 ...
Page 121: ... 112 VII Control GB HWE10130 ...
Page 123: ... 114 ...
Page 159: ... 150 ...
Page 259: ... 250 IX Troubleshooting GB HWE10130 ...
Page 261: ... 252 ...