IX
Troubleshooting ]
- 182 -
HWE10130
GB
1. Error
Code
Open-circuited IPM/Loose ACCT connector (Detail code 119)
2. Error
definition and error detection method
Presence of enough current cannot be detected during the self-diagnostic operation immediately before inverter startup.
3. Cause, check method and remedy
Refer to section -6- "Inverter" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 234)
1. Error
Code
Faulty ACCT wiring (Detail code 120)
2. Error
definition and error detection method
Presence of target current cannot be detected during the self-diagnostic operation immediately before startup. (Detection of
improperly mounted ACCT sensor)
3. Cause, check method and remedy
Refer to section -6- "Inverter" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 234)
5301
Cause
Check method and remedy
(1)
Inverter output wiring problem
Check output wiring connections.
Confirm that the U- and W-phase output cables are put through CT12
and CT22 on the INV board respectively.
(2)
Inverter failure
Refer to IX [4] -6- (2) [3], [4].(page 237)
(3)
Compressor failure
Refer to IX [4] -6- (2) [2].(page 236)
5301
Cause
Check method and remedy
(1)
Inverter output wiring problem
Check output wiring connections.
Confirm that the U- and W-phase output cables are put through CT12
and CT22 on the INV board respectively.
(2)
Inverter failure
Refer to IX [4] -6- (2) [3], [4].(page 237)
(3)
Compressor failure
Refer to IX [4] -6- (2) [2].(page 236)
Summary of Contents for PUHY-RP200
Page 9: ...HWE10130 GB ...
Page 11: ... 2 ...
Page 21: ... 12 I Read Before Servicing GB HWE10130 ...
Page 23: ... 14 ...
Page 63: ... 54 II Restrictions GB HWE10130 ...
Page 65: ... 56 ...
Page 75: ... 66 ...
Page 83: ... 74 IV Remote Controller GB HWE10130 ...
Page 85: ... 76 ...
Page 89: ... 80 ...
Page 95: ... VI Refrigerant Circuit 86 HWE10130 GB ...
Page 97: ... 88 ...
Page 121: ... 112 VII Control GB HWE10130 ...
Page 123: ... 114 ...
Page 159: ... 150 ...
Page 259: ... 250 IX Troubleshooting GB HWE10130 ...
Page 261: ... 252 ...