VII
Control ]
- 96 -
HWE10130
GB
-5- Bypass Control
Bypass solenoid valves (SV1(a,b)), which bypass the high- and low- pressure sides, perform the following functions.
(1) Bypass solenoid valve (SV1a) (ON = Open)
(2) Bypass solenoid valve (SV1b) (ON = Open)
Operation
SV1a
ON OFF
At compressor startup
ON for 4 minutes.
After the restoration of thermo or 3 minutes
after restart
ON for 4 minutes.
During cooling or heating operation with the
compressor stopped
Always OFF
After the operation has stopped
Always OFF
During defrost operation
Always ON
During refrigerant oil recovery
SV1a turns off during refrigerant oil recovery that takes place after a low-
frequency operation (both in the cooling and heating modes).
When the low pressure (63LS) drops
SV1a turns on if the low pressure
(63LS) drops below 0.23 MPa while
the compressor is operating at the
minimum frequency.
SV1a turns off if the low pressure
(63LS) reaches 0.38 MPa or above.
Operation
SV1b
ON OFF
At compressor startup
ON for 4 minutes.
After the restoration of thermo or 3 minutes
after restart
ON for 4 minutes.
During cooling mode and when the com-
pressor is not in operation
SV1b turns on for three minutes, and turns on when the formula LPS -
LPS
≤
0.2 MPa is satisfied.
During heating mode and when the com-
pressor is not in operation
Always OFF
After the operation has stopped
SV1b turns on for three minutes, and turns on when the formula LPS -
LPS
≤
0.2 MPa is satisfied.
During defrost operation
Always ON
During refrigerant oil recovery
SV1a turns off during refrigerant oil recovery that takes place after a low-
frequency operation (both in the cooling and heating modes).
When the low pressure (63LS) drops
SV1a turns on if the low pressure
(63LS) drops below 0.23 MPa while
the compressor is operating at the
minimum frequency.
SV1a turns off if the low pressure
(63LS) reaches 0.38 MPa or above.
Summary of Contents for PUHY-RP200
Page 9: ...HWE10130 GB ...
Page 11: ... 2 ...
Page 21: ... 12 I Read Before Servicing GB HWE10130 ...
Page 23: ... 14 ...
Page 63: ... 54 II Restrictions GB HWE10130 ...
Page 65: ... 56 ...
Page 75: ... 66 ...
Page 83: ... 74 IV Remote Controller GB HWE10130 ...
Page 85: ... 76 ...
Page 89: ... 80 ...
Page 95: ... VI Refrigerant Circuit 86 HWE10130 GB ...
Page 97: ... 88 ...
Page 121: ... 112 VII Control GB HWE10130 ...
Page 123: ... 114 ...
Page 159: ... 150 ...
Page 259: ... 250 IX Troubleshooting GB HWE10130 ...
Page 261: ... 252 ...