VII
Control ]
- 92 -
HWE10130
GB
2. Function of the switch (Indoor unit)
(1) Dipswitches
1) SW1,3
2) SW2
SW3-1
OFF
OFF
OFF
ON
ON
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
Very Low
Low
Preset speed
Preset speed
Preset speed
Stop
Stop
Stop
Stop
Switch setting
SW1-7 SW1-8
Heating
Cooling
Cooling-only/heat pump
Heat pump
Cooling-only
Heat pump
Fan speed during Thermo-OFF
Note 2. If both SW1-7 and SW1-8 are set to ON, the fan remains stopped during heating Thermo-OFF.
To prevent incorrect temperature detection due to a build-up of warm air around the indoor unit, use the built-in temperature sensor on the remote controller (SW1-1)
instead of the one on the indoor unit inlet thermistor.
Note 3. By setting SW3-1, SW1-7, and SW1-8 to a certain configuration, the fan can be set to remain stopped during cooling Thermo-OFF. See the table below for details.
Switch
Function
Function according to switch setting
OFF
ON
Switch setting timing
OFF
ON
Notes
SW1
SW3
1
2
3
4
5
6
7
8
9
10
9
10
1
2
3
4
5
6
7
8
Room temperature
detection position
Clogged filter detection
Filter check reminder time setting
Outside air intake
Remote display option
Humidifier control
Self-recovery after power failure
Fan speed setting for
Heating Thermo-OFF
Power source start-stop
Unit model selection
Louver
Vane
Vane swing function
-
Vane angle limit setting
for cooling operation
Initial vane position
Heating 4°C [7.2°F] up
Automatic LEV value
conversion function
Indoor unit inlet
100h
Disabled
Fan output
2500h
Enabled
Thermo-ON signal
Built-in sensor on
the remote controller
Available
During heating operation
According to the
SW1-7 setting
Heat pump
Always on while in the heating mode
Fan speed setting for
Heating Thermo-OFF
Very Low
Low
Preset speed
Cooling only
Enabled
Enabled
Disabled
Disabled
Enabled
Enabled
Not available
Available
Not available
Available
Not available
Not available
Available
Not available
Available
Not available
Available
-
-
-
-
-
Downblow B,C
Horizontal
While the unit is stopped
(Remote controller OFF)
Always set to OFF on PKFY-VBM model units
Set to ON (built-in sensor on the remote controller)
on All Fresh (PEFY-VMH-F) model units
Applicable to All Fresh model units
(PEFY-VMH-F) only
Applicable to All Fresh model units
(PEFY-VMH-F) only
Always set to OFF on PKFY-VBM model units
PLFY-VLMD model only
Set to OFF on floor-standing
(PFFY) type units
Always set to Downblow B or C on
PKFY-VBM model units
Disabled
SHm setting
2°C [3.6°F]
10°C [18°F]
5°C [9°F]
15°C [27°F]
The setting depends on the
model and type.
The setting depends on the
model and type.
SCm setting
Disabled
Forced heating operation
at OA temp of 5 C or below
-
-
-
Note 1. Settings in the shaded areas are factory settings.(Refer to the table below for the factory setting of the switches whose factory settings are not indicated by the shaded cells.)
1 2 3 4 5 6
P20
4
P25
5
P32
6
P40
8
P50
10
ON
OFF
1 2 3 4 5 6
P15
3
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
P63
13
P71
14
P80
16
P100
20
P125
25
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
P200
40
P250
50
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
P140
28
ON
OFF
Model
Capacity (model) code
SW2
setting
Note. The setting timing for SW2 is before power is turned on.
Summary of Contents for PUHY-RP200
Page 9: ...HWE10130 GB ...
Page 11: ... 2 ...
Page 21: ... 12 I Read Before Servicing GB HWE10130 ...
Page 23: ... 14 ...
Page 63: ... 54 II Restrictions GB HWE10130 ...
Page 65: ... 56 ...
Page 75: ... 66 ...
Page 83: ... 74 IV Remote Controller GB HWE10130 ...
Page 85: ... 76 ...
Page 89: ... 80 ...
Page 95: ... VI Refrigerant Circuit 86 HWE10130 GB ...
Page 97: ... 88 ...
Page 121: ... 112 VII Control GB HWE10130 ...
Page 123: ... 114 ...
Page 159: ... 150 ...
Page 259: ... 250 IX Troubleshooting GB HWE10130 ...
Page 261: ... 252 ...