IX
Troubleshooting ]
- 154 -
HWE10130
GB
[2] Responding to Error Display on the Remote Controller
1. Error
Code
Serial communication error
2. Error
definition and error detection method
Serial communication error between the control board and the INV board on the compressor, and between the control board
and the Fan board
Detail code 01: Between the control board and the INV board
Detail code 05: Between the control board and the Fan board
3. Cause, check method and remedy
(1) Faulty wiring
Check the following wiring connections.
1) Between Control board and Fan board
2) Between Fan board and INV board
(2) INV board failure, Fan board failure and Control board failure
Replace the INV board or the Fan board or control board when the power turns on automatically, even if the power source is
reset.
Refer to section -6- "Inverter" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 234)
0403
CN2
CN21
CN4
CN5
CN332
CN18V
Control board FAN board
CN22
CN2
CN5V
CN4
CN4
FAN board
INV board
Summary of Contents for PUHY-RP200
Page 9: ...HWE10130 GB ...
Page 11: ... 2 ...
Page 21: ... 12 I Read Before Servicing GB HWE10130 ...
Page 23: ... 14 ...
Page 63: ... 54 II Restrictions GB HWE10130 ...
Page 65: ... 56 ...
Page 75: ... 66 ...
Page 83: ... 74 IV Remote Controller GB HWE10130 ...
Page 85: ... 76 ...
Page 89: ... 80 ...
Page 95: ... VI Refrigerant Circuit 86 HWE10130 GB ...
Page 97: ... 88 ...
Page 121: ... 112 VII Control GB HWE10130 ...
Page 123: ... 114 ...
Page 159: ... 150 ...
Page 259: ... 250 IX Troubleshooting GB HWE10130 ...
Page 261: ... 252 ...