IX
Troubleshooting ]
- 165 -
HWE10130
GB
1. Error
Code
Water supply cutoff
2. Cause, check method and remedy
2601
Cause
Check method and remedy
(1)
The water tank of the humidifier is empty.
Check the amount of supply water.
Check for the solenoid valve and for the connection.
(2)
The solenoid valve for humidification is OFF.
Check the connector.
(3)
Disconnected float switch
Check the connecting part.
(4)
Poor operation of float switch
Check for the float switch.
(5)
Frozen water tank
Turn off the power source of the water tank to defrost, and
turn it on again.