9. OPTIONAL PARTS
HEAT SOURCE
164
WR2
MEE15K036
9-3. JOINT KIT "CMY-R160-J1" FOR BC CONTROLLER
CMY-Y102SS-G2
Fig.1. CMY-R160-J1 applying scheme
1. Designing CMY-R160-J1 to a PURY/PQRY system
The maximum down-stream Indoor capacity for 1 port of BC
controller is P80. When the down-stream Indoor capacity is
above P80, Joint kit CMY-R160-J1 is needed to combined 2
ports of BC controller to enlarge the capacity, like Group 2 and
3 in Fig. 1.
Maximum 3 Indoor units are allowed to connect to 1 port of BC
controller or 2 combined ports of BC controller using CMY-
R160-J1.
When connecting Indoor units to 1 port of BC controller or 2
combined ports of BC controller using CMY-R160-J1 or CMY-
Y102SS-G2 is applicable, like Group 1 and 2 in Fig. 1
Caution: Mixed cooling and heating mode at the same time for
Indoor units connecting to 1 port or 2 combined ports is not
available.
2. Piping at the installation site
The connection of CMY-R160-J1 to BC controller and pipe leading to Indoor units is referable to Fig. 2. Non-oxidized brazing is
necessary. All piping must be careful to avoid foreign material getting inside.
After piping and air-tight testing, insulation work to the Joint and pipe should be done. Details is available at the Installation Manual.
Joint kit "CMY-R160-J1" for BC controller is used to combine 2 ports of the BC controller at a PURY/PQRY system so as to
enable down-stream Indoor capacity above P80 as shown in Fig. 1.
ø15.88(5/8")
ø9.52(3/8")
ø19.05(3/4")
ø9.52(3/8")
ø15.88(5/8")
ø9.52(3/8")
226(8-29/32")
226(8-29/32")
60(2-3/8")
60(2-3/8")
Instruction
This sheet
Please prepare the following items in the field.
Tape for insulation material sealing
Extension pipe for refrigerant circuit
1pc
1pc
1pc
1pc for gas side
1pc for Iiquid side
8pcs
1pc
1pc
2pcs
Cover 1
Cover 2
Cover 3
Band
Reducer 2
Joint pipe(Small)
Joint pipe(Large)
7
9
Reducer 1
8
6
5
4
3
2
2
1
1
OD19.05-ID22.2 OD19.05-ID15.88
The Joint kit include following items:
Cutting point
Have pipe expansion of indoor unit connecting port by
cutting the piping at the cutting point.
Remove burr after cutting the piping to prevent entering
the piping.
Check that there is no crack at the pipe expansion part.
2 Joint pipe (for liquid side)
3 Joint pipe (for gas side)
mm (in.)
Outdoor/Heat source unit
Joint kit
CMY-R160-J1
Joint
BC controller
IU
IU
IU
IU
IU
IU
IU
Group1
Total Indoor Capacity
<=P80
Group2
Total Indoor Capacity
P81 to P250
Group3
Indoor Capacity
P100 to P250
Piping to indoor unit
(Non-oxidized brazing)
Joint pipe (for liquid side)
2
Joint pipe(for gas side)
3
Fig.2. Connecting CMY-R160-J1
0000003811.BOOK 164 ページ 2015年11月9日 月曜日 午前11時20分