1. SPECIFICATIONS
HEAT SOURCE
96
WR2
MEE15K036
Model
PQRY-P550YSLM-A
Power source
3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity
*1 kW
63.0
(Nominal)
kcal/h
55,000
*1 BTU/h
215,000
Power input
kW
11.55
Current input
A
19.4-18.5-17.8
EER
kW/kW
5.45
Temp. range of
Indoor
W.B.
15.0~24.0°C (59~75°F)
cooling
Circulating water
°C
10.0~45.0°C (50~113°F)
Heating capacity
*2 kW
69.0
(Nominal)
kcal/h
60,000
*2 BTU/h
235,400
Power input
kW
11.31
Current input
A
19.0-18.1-17.4
COP
kW/kW
6.10
Temp. range of
Indoor
D.B.
15.0~27.0°C (59~81°F)
heating
Circulating water
°C
10.0~45.0°C (50~113°F)
Indoor unit
Total capacity
50~150% of heat source unit capacity
connectable
Model/Quantity
P15~P250/2~50
Sound pressure level (measured in anechoic room)
dB <A>
55
Sound power level (measured in anechoic room)
dB <A>
69
Refrigerant
High pressure
mm (in.)
22.2 (7/8) Brazed (28.58 (1-1/8) Brazed for the part that exceeds 65 m)
piping diameter
Low pressure
mm (in.)
28.58 (1-1/8) Brazed
Set Model
Model
PQRY-P300YLM-A
PQRY-P250YLM-A
Circulating water
Water flow rate
m
3
/h
5.76 + 5.76
L/min
96 + 96
cfm
3.4 + 3.4
Pressure drop
kPa
24
24
Operating volume range
m
3
/h
3.0 + 3.0 ~ 7.2 + 7.2
Compressor
Type
Inverter scroll hermetic compressor
Inverter scroll hermetic compressor
Manufacture
AC&R Works, MITSUBISHI ELECTRIC CORPORATION
AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method
Inverter
Inverter
Motor output
kW
7.7
6.2
Case heater
kW
-
-
Lubricant
MEL32
MEL32
External finish
Galvanized steel sheets
Galvanized steel sheets
External dimension H x W x D
mm
1,100 x 880 x 550
1,100 x 880 x 550
in.
43-5/16 x 34-11/16 x 21-11/16
43-5/16 x 34-11/16 x 21-11/16
Protection devices
High pressure protection
High pressure sensor, High pressure switch at 4.15 MPa (601
psi)
High pressure sensor, High pressure switch at 4.15 MPa (601
psi)
Inverter circuit (COMP.)
Over-heat protection, Over-current protection
Over-heat protection, Over-current protection
Compressor
Over-heat protection
Over-heat protection
Refrigerant
Type x original charge
R410A x 5.0 kg (12 lbs)
R410A x 5.0 kg (12 lbs)
Control
Indoor LEV and BC controller
Net weight
kg (lbs)
172 (380)
172 (380)
Heat exchanger
plate type
plate type
Water volume in plate
I
5.0
5.0
Water pressure Max.
MPa
2.0
2.0
HIC circuit (HIC: Heat Inter-Changer)
-
-
Pipe between unit and
High pressure
mm (in.)
19.05 (3/4) Brazed
19.05 (3/4) Brazed
distributor
Low pressure
mm (in.)
22.2 (7/8) Brazed
22.2 (7/8) Brazed
Drawing
External
WKS94C749
Wiring
WKE94G131
WKE94G131
Standard attachment
Document
Installation Manual
Accessory
Refrigerant conn. pipe
Optional parts
Heat Source Twinning kit: CMY-Q100CBK2
Joint: CMY-Y102SS/LS-G2, CMY-R160-J1
Main BC controller: CMB-P108, 1010, 1013, 1016V-GA1
Sub BC controller: CMB-P104, 108V-GB1, CMB-P1016V-HB1
Remarks
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred
to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.
The ambient temperature of the heat source unit needs to be kept below 40°C D.B.
The ambient relative humidity of the heat source unit needs to be kept below 80%.
The heat source unit should not be installed at outdoor.
Be sure to mount a strainer (more than 50 meshes) at the water inlet piping of the unit.
Be sure to provide interlocking for the unit operation and water circuit.
The heat source twinning kit (low pressure) should be connected to the low pressure side of the heat source unit.
Install the supplied insulation material to the unused drain-socket.
When installing insulation material around both water and refrigerant piping, follow the installation manual.
When the high pressure piping length is 65 m or less, use 22.2 (7/8) pipe. When the high pressure piping length exceeds
65 m, use 22.2 (7/8) pipe until 65 m, use 28.58 (1-1/8) pipe for the part that exceeds 65 m.
Notes:
Unit converter
1.Nominal cooling conditions (subject to JIS B8615-2)
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Water temperature: 30°C (86°F)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-2)
Indoor: 20°CD.B. (68°FD.B.) ,Water temperature: 20°C (68°FD.B.)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
BTU/h
=kW x 3,412
cfm
=m
3
/min x 35.31
lbs
=kg/0.4536
*Above specification data is
subject to rounding variation.