107
2. EXTERNAL DIMENSIONS
HEAT SOURCE
WR2
MEE15K036
PQRY-P700, 750, 800, 850, 900YSLM-A
Unit: mm
Heat Source unit
2
Heat Source unit 1
880
20
880
550
1450
1780
T
winning pipe (High pressure)
b
e
a
c
d
To BC controller
<Optional parts>
To BC controller
<Optional parts>
Twinning pipe (Low pressure)
T
winning pipe connection size
Note 1.Connect the pipes as shown in the figure above. Refer to the table below for the pipe size.
2.T
winning pipe (High pressure) should not be tilted more than 15 degrees from the horizontal plane.
3.See the Installation Manual for the details of
T
winning pipe installation.
4.Only use the
T
winning pipe by Mitsubishi (optional parts).
Package unit name
Component unit name
Heat Source unit 1
Twinning pipe Kit(optional parts)
Heat Source unit 2
CMY
-Q200CBK
Twinning pipe~Heat source unit
Unit model
High pressure
Low pressure
c or e
d
P350
P400
ø
22.2
BC controller~T
winning pipe
High pressure
Low pressure
a
b
ø
28.58
PQR
Y-P700YSLM-A
PQR
Y-P350YLM-A
PQR
Y-P350YLM-A
PQR
Y-P750YSLM-A
PQR
Y-P400YLM-A
PQR
Y-P350YLM-A
PQR
Y-P800YSLM-A
PQR
Y-P400YLM-A
PQR
Y-P400YLM-A
ø
34.93
ø
41.28
ø
28.58
PQR
Y-P850YSLM-A
PQR
Y-P450YLM-A
PQR
Y-P400YLM-A
PQR
Y-P900YSLM-A
PQR
Y-P450YLM-A
PQR
Y-P450YLM-A
P450