53
WY
MEE15K036
7. CAPACITY TABLES
HEAT SOURCE
7-2. Correction by total indoor
CITY MULTI system have different capacities and inputs when many combinations of indoor units with different total capacities
are connected. Using following tables, the maximum capacity can be found to ensure the system is installed with enough capacity
for a particular application.
Total capacity of indoor units
50
100
200
150
250
300
Ratio of capacity
Ratio of power input
0.2
1.2
1.0
0.8
0.6
0.4
1.0
0.8
0.6
0.4
0.2
1.2
Total capacity of indoor units
100
150
250
200
300
350
0.2
1.2
1.0
0.8
0.6
0.4
1.0
0.8
0.6
0.4
0.2
1.2
Ratio of capacity
Ratio of power input
PQHY-P250YLM-A
PQHY-P200YLM-A
Cooling
Heating
Cooling
Heating
Nominal
Cooling
Capacity
Input
kW
BTU/h
kW
PQHY-P250YLM-A
28.0
95,500
4.90
Nominal
Heating
Capacity
Input
kW
BTU/h
kW
PQHY-P250YLM-A
31.5
107,500
5.08
Nominal
Cooling
Capacity
Input
kW
BTU/h
kW
PQHY-P200YLM-A
22.4
76,400
3.71
Nominal
Heating
Capacity
Input
kW
BTU/h
kW
PQHY-P200YLM-A
25.0
85,300
3.97