S.D. WY
MEE15K036
2. M-NET control
SYSTEM DESIGN
2. Address should be set to Indoor units and centralized controller.
3. For a system having more than 32 indoor unit (P15-P140), confirm the need of Booster at
2-3 "System configuration restrictions".
4. When a PAR-3X MAA series (X indicates 1, 2…) is connected to a group, no other MA remote controllers can be connected to the
same group.
NOTE:
*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.
*SC can be connected to TB3 side or TB7 side;
Should SC connected to TB7 side, change Jumper from CN41 to CN40 at the Heat source unit module so as to supply power to the SC.
1. Heat source units OC and OS in one refrigerant circuit system are automatically detected.
OC and OS are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order of their
address.
2-4-3-2. MA remote controller, Single-refrigerant-system, System Controller
Indoor unit
MA R/C
MA R/C
(Main)
(Sub)
MA R/C
01
02
03
04
05
TB15
TB5
TB5
TB5
TB5
TB5
MA R/C
TB15
TB15
TB15
TB15
SRU
Wireless R/C
1*
1*
Group 2
Group 1
Group 3
Group 4
TB3
TB3
201
52
51
OC
OS
SC
TB3
TB3
52
51
OC
OS
TB3
51
OC
CN41
CN40
CN41
CN40
CN41
CN40
CN41
CN40
CN41
CN40
ON
DipSW5-1
ON
DipSW5-1
ON
DipSW5-1
ON
DipSW5-1
ON
DipSW5-1
<Two heat source units>
<Two heat source units>
<One heat source unit>
PQHY
PQHY
PQHY