S.D. WY
MEE15K036
2. M-NET control
SYSTEM DESIGN
2-2. Transmission cable specifications
Type of cable
Cable size
Remarks
Sheathed 2-core cable (unshielded) CVV
Shielding wire (2-core)
CVVS, CPEVS or MVVS
Transmission cables (L
i
)
M-NET remote controller cables (e
i
)
CVVS, MVVS: PVC insulated PVC sheathed shielded control cable
CPEVS: PE insulated PVC sheathed shielded communication cable
CVV: PVC insulated PVC sheathed control cable
*1 To wire PAR-3X MAA series (X indicates 1, 2…) and Simple
MA remote controller use a wire with a diameter of 0.3 mm
2
[AWG22]
MA Remote controller cables (a
i
)
When 10 m [32ft] is exceeded, use cables with
the same specification as transmission cables.
More than 1.25 mm
2
[AWG16]
0.3 1.25 mm [AWG22 16]
2
Max length: 200 m [656ft]
Max length: within 200 m
2
0.3 1.25 mm [AWG22 16]*1