11-4. TROUBLESHOOTING CHECK TABLE
MXZ-2D
No.
1
2
3
4
5
6
8
9
10
11
12
13
14
15
Symptom
'Outdoor
unit stops
and restarts
3 minutes
later' is
repeated.
Primary current protection
Secondary current protection
High-pressure protection
Defrosting in cooling
3 times
Lighted
Discharge temperature
protection
4 times
Lighted
Low discharge
temperature protection
• Check refrigerant circuit and refrigerant amount.
• Refer to 11-6.
"Check of LEV".
• Refer to 11-6.
"Check of outdoor thermistors".
• Refer to 11-6.
"Check of LEV".
• Check refrigerant circuit and refrigerant amount.
These symptoms do not mean any abnormality of the
product, but check the following points.
• Check if indoor filters are clogged.
• Check if refrigerant is short.
• Check if indoor/outdoor unit air circulation is short cycled.
Twice
Lighted
Once
Lighted
The discharge temperature exceeds 100°C during operation.
The frequency of the compressor is kept 68 Hz
(MXZ-2D33VA, MXZ-2D40
VA)/
80 Hz
(MXZ-2D53VA/H)
or more and the discharge temperature is kept
under 50°C (COOL mode)/40°C (HEAT mode) for more than 40 minutes.
The input current exceeds 8 A
(MXZ-2D33VA)
/ 10 A
(MXZ-2D40VA,
MXZ-2D53VA/H).
The current of the compressor exceeds 17 A.
The indoor gas pipe temperature exceeds 45°C during heating.
The indoor gas pipe temperature falls 3°C or below during cooling.
Outdoor unit
operates.
16
17
18
19
7
LED1(Red) LED2(Yellow)
Lighted
Twice
Outdoor power system
Lighted
3 times
Discharge temperature
thermistor
Outdoor heat exchanger
temperature thermistor
Defrost thermistor
Lighted
7 times
Nonvolatile memory data
• Replace the inverter P.C. board.
Abnormal point / Condition
Remedy
A short circuit is detected in the thermistor during operation, or when
an open circuit is detected in the thermistor after 5 minutes (in cooling)
and 10 minutes (in heating) of compressor start-up.
A short circuit is detected in the thermistor during operation, or when an
open circuit is detected in the thermistor after 5 minutes of compressor
start-up.
• Replace the inverter P.C. board.
Indication
Overcurrent protection cut-out operates 3 consecutive times
within 1 minute after the compressor gets started.
A short circuit is detected in the thermistor during operation, or when an
open circuit is detected in the thermistor after 10 minutes of compressor
start-up.
Condition
The nonvolatile memory data cannot be read properly.
Fin temperature
thermistor
P.C board temperature
thermistor
Lighted
4 times
Ambient temperature
thermistor
A short or open circuit is detected in the thermistor during operation.
A short or open circuit is detected in the thermistor during operation.
5 times
Lighted
Overcurrent
3 times
Not lighted
Discharge temperature
protection
Fin temperature
protection
P.C. board temperature
protection
High-pressure
protection
• Replace the inverter P.C. board.
Bus-bar voltage
protection
Not lighted
Outdoor fan motor
8 times
Not lighted
Current sensor
protection
• Replace the inverter P.C. board.
Not lighted
Compressor
• Refer to 11-6.
"Check of outdoor fan motor".
• Reconnect compressor connector.
• Refer to 11-6.
"How to check inverter/compressor".
• Check the stop valve.
• Check the amount of gas and the refrigerant circuit.
• Check the stop valve.
• Check the amount of gas and refrigerant circuit.
• Refer to 11-6.
"Check of LEV".
• Check refrigerant circuit and refrigerant amount.
• Refer to 11-6.
"Check of outdoor fan motor".
• Reconnect compressor connector.
• Refer to 11-6.
"How to check inverter/compressor".
• Check the stop valve.
Twice
Not lighted
4 times
Not lighted
5 times
Not lighted
9 times
Not lighted
14 A
(MXZ-2D33VA)
/18 A
(MXZ-2D40VA, MXZ-2D53VA/H
) current flows
into intelligent power module.
The bus-bar voltage exceeds 430 V or falls to 50 V or below during
compressor operating.
Discharge temperature exceeds 116°C during operation. Compressor can
restart if discharge temperature thermistor reads 100°C or less 3 minutes
later.
The fin temperature exceeds 90°C during operation.
The P.C. board temperature exceeds 78°C during operation.
Failure occurs 3 consecutive times within 30 seconds after the fan
gets started.
A short or open circuit is detected in the current sensor during
compressor operating.
The compressor does not synchronize with the operating power.
The outdoor heat exchanger temperature exceeds 70°C during cooling
or indoor gas pipe temperature exceeds 70°C during heating.
Outdoor unit
does not
operate.
Lighted
Once
LEV and drain pump
• Check the connection of the compressor connecting
wire.
• Refer to 11-6.
"How to check inverter/compressor".
• Check the stop valve.
• Refer to 11-6.
"Check of outdoor thermistors".
• Refer to 11-6.
"Check of outdoor thermistors".
• Refer to 11-6.
"Check of outdoor thermistors".
• Refer to 11-6.
"Check of LEV".
• Check the drain pump of the indoor unit.
The indoor unit detects an abnormality in the LEV and drain pump.
Lighted
11 times
Stop valve
Closed valve
Closed valve is detected by compressor current.
(MXZ-2D33VA, MXZ-2D40VA)
• Check the stop valve.
13 times
10 times
OBH626B
Summary of Contents for MXZ-2D33VA-E1
Page 16: ...16 OUTLINES AND DIMENSIONS 5 MXZ 2D33VA MXZ 2D40VA MXZ 2D53VA MXZ 2D53VAH Unit mm OBH626B ...
Page 20: ...20 WIRING DIAGRAM 6 MXZ 2D33VA MXZ 2D40VA MXZ 2D53VA OUTDOOR DISPLAY P C BOARD OBH626B ...
Page 21: ...21 MXZ 2D53VAH OUTDOOR DISPLAY P C BOARD OBH626B ...
Page 22: ...22 MXZ 3D54VA OBH626B ...
Page 23: ...23 MXZ 3D68VA OBH626B ...
Page 24: ...24 MXZ 4D72VA OBH626B ...
Page 25: ...25 MXZ 4D83VA OBH626B ...
Page 26: ...26 MXZ 5D102VA OBH626B ...