Check of power supply
• When outdoor unit does not operate, LED on outdoor P.C. board is not lighting.
11-6. TROUBLESHOOTING FLOW
Turn ON the breaker.
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
+
-
Check the main power supply circuit for proper connections.
Is there voltage of 230V AC in the
power supply terminal block?
Is there voltage of 230V AC between
LD66B and X64 on the inverter
P.C. board?
Check the power supply and correct them.
Replace the outdoor disply P.C. board.
Replace the inverter P.C. board.
Is there voltage of 230V AC between
LD66A and LD70 on the inverter
P.C. board?
Replace the reactor.
Is there voltage of 325V DC between
DB61 and DB61 on the inverter
P.C. board?
Replace the inverter P.C. board.
Is there voltage of 5V DC between
CN936 and CN936 on the
outdoor display P.C. board?
Check the conneced wire between
the inverter P.C. board and outdoor
display P.C. board and correct it.
Replace the inverter P.C. board.
MXZ-2D33VA/2D40VA/2D53VA/2D53VAH
OBH626B