69
3. Outdoor unit failure mode table
MXZ-2D
Upper or
left lamp of
OPERATION
INDICATOR
lamp (Indoor
unit)
Abnormal point
(Failure mode/protection)
LED indication
(Outdoor P.C. board)
Condition
Remedy
Indoor/
outdoor
unit failure
mode
recall
function
LED 1
LED 2
OFF
None (Normal)
Not lighted Not lighted —
—
—
2-time f ash
Outdoor power system
Lighted
Lighted Overcurrent protection cut-out operates
3 consecutive times within 1 minute
after the compressor gets started.
Compressor protection cut-out
operates 24 consecutive times within
10 seconds after the compressor gets
started.
• Check the compressor con-
necting wire.
• Refer to 11-6. "Check of
inverter/compressor".
• Check the stop valve.
○
3-time f ash
Discharge temperature
thermistor
Lighted
Once
Thermistor shorts or opens during
compressor running.
• Refer to 11-6. "Check of
outdoor thermistors".
○
Defrost thermistor
Lighted
Once
○
Ambient temperature
thermistor
Lighted
Twice
○
Fin temperature thermistor
Lighted
3 times
○
P.C. board temperature
thermistor
Lighted
4 times
• Replace the inverter P.C.
board.
○
Outdoor heat exchanger
temperature thermistor
Lighted
9 times
• Refer to 11-6. "Check of
outdoor thermistors".
○
4-time f ash
Overcurrent
Once
Not
lighted
The overcurrent f ows into intelligent
power module.
• Check the compressor con-
necting wire.
• Refer to 11-6. "Check of
inverter/compressor".
• Check the stop valve.
—
Compressor
Twice
Not
lighted
The overcurrent f ows into intelligent
power module within 10 seconds after
the compressor gets started.
( The compressor gets restarted in
15 seconds.)
• Check the compressor con-
necting wire.
• Refer to 11-6. "Check of
inverter/compressor".
—
9 times
Not
lighted
Waveform of compressor current is dis-
torted.
—
5-time f ash
Discharge temperature
Lighted
Lighted Discharge temperature exceeds 116 ºC
during operation.
• Check refrigerant circuit and
refrigerant amount.
• Refer to 11-6. "Check of
LEV".
—
6-time f ash
High pressure
Lighted
Lighted The outdoor heat exchanger tempera-
ture exceeds 70 ºC during cooling or
the indoor gas pipe temperature ex-
ceeds 70 ºC during heating.
• Check refrigerant circuit and
refrigerant amount.
• Check the stop valve.
—
7-time f ash
Fin temperature
3 times
Not
lighted
The f n temperature exceeds 90 ºC
during operation.
• Check around outdoor unit.
• Check outdoor unit air pas-
sage.
—
P.C. board temperature
4 times
Not
lighted
The P.C. board temperature exceeds
80 ºC during operation.
• Refer to 11-6. "Check of
outdoor fan motor".
—
8-time f ash
Outdoor fan motor
Lighted
Lighted Failure occurs 3 consecutive times
within 30 seconds after the fan gets
started.
• Refer to 11-6. "Check of
outdoor fan motor".
—
9-time f ash
Nonvolatile memory data
Lighted
5 times Nonvolatile memory data cannot be
read properly.
• Replace the inverter P.C.
board.
○
Power module
7 times
Not
lighted
The output of the power module that
drove the compressor was shorted or
the winding of the compressor was
shorted.
• Refer to 11-6. "Check of
inverter/compressor".
○
10-time f ash
Discharge temperature
Lighted
Lighted The discharge temperature is kept
under 50 ºC (COOL mode)/40 ºC (HEAT
mode) for more than 40 minutes.
• Check refrigerant circuit and
refrigerant amount.
• Refer to 11-6. "Check of
LEV".
—
11-time f ash
Current sensor
8 times
Not
lighted
The sensor circuit of current of
compressor shorts or opens during
compressor operate.
• Replace the inverter P.C.
board.
○
Bus-bar voltage
6 times
Not
lighted
The bus-bar voltage exceeds 430 V or
falls to 50 V or below during compres-
sor operating.
• Check the power supply.
• Replace the inverter P.C.
board.
○
14-time f ash
Stop valve
Lighted 12 times The current of compressor is power
module is out of order.
• Check the stop valve.
• Check refrigerant circuit and
refrigerant amount.
○
NOTE:
Blinking patterns of this mode differ from the ones of Troubleshooting check table (11-4).
OBH626B
Summary of Contents for MXZ-2D33VA-E1
Page 16: ...16 OUTLINES AND DIMENSIONS 5 MXZ 2D33VA MXZ 2D40VA MXZ 2D53VA MXZ 2D53VAH Unit mm OBH626B ...
Page 20: ...20 WIRING DIAGRAM 6 MXZ 2D33VA MXZ 2D40VA MXZ 2D53VA OUTDOOR DISPLAY P C BOARD OBH626B ...
Page 21: ...21 MXZ 2D53VAH OUTDOOR DISPLAY P C BOARD OBH626B ...
Page 22: ...22 MXZ 3D54VA OBH626B ...
Page 23: ...23 MXZ 3D68VA OBH626B ...
Page 24: ...24 MXZ 4D72VA OBH626B ...
Page 25: ...25 MXZ 4D83VA OBH626B ...
Page 26: ...26 MXZ 5D102VA OBH626B ...