86
Check of R.V. coil
No
Yes
No
Yes
Yes
No
1. Disconnect the lead wire leading to the compressor.
2. 3 minutes after turning ON the breaker, start EMERGENCY
OPERATION in HEAT mode.
Is there voltage of 230V AC between pin 1 and
pin 2 at connector CN721?
Turn OFF the breaker. Disconnect the connector CN721.
Replace the inverter P.C. board.
Replace the 4-way valve.
Replace the R.V. coil.
Is there normal resistance
to R.V. coil?
(Refer to 11-5.)
1. Disconnect the lead wire leading to the compressor.
2. 3 minutes after turning ON the breaker, start EMERGENCY
OPERATION in COOL mode.
Is there voltage of 230V AC between pin 1 and
pin 2 at connector CN721?
Replace the inverter P.C. board.
Replace the 4-way valve.
• The heating operation does not operate.
• The cooling operation does not operate.
The cooling operation or the heating operation does not operate.
MXZ-2D33VA/2D40VA/2D53VA/2D53VAH
MXZ-2D
CN721
Inverter P.C. board
OBH626B