![Mitsubishi Electric MR-J5D User Manual Download Page 127](http://html.mh-extra.com/html/mitsubishi-electric/mr-j5d/mr-j5d_user-manual_1811806127.webp)
6 OPTIONS AND PERIPHERAL EQUIPMENT
6.4 Molded-case circuit breakers, fuses
125
6
For branch wiring of the control circuit power supply
■
400 V class
*1 To comply with the IEC/EN/UL/CSA standards, refer to the MR-J5D Safety Instructions and Precautions for AC Servos (IB(NA)-
0300527) for selection of molded-case circuit breakers and fuses.
Selection examples that comply with IEC/EN/UL 61800-5-1 and
CSA C22.2 No.274
The semiconductor fuses and recommended wire gauges in the tables are selections based on the rated I/O of the converter
unit/drive unit.
Semiconductor fuse
■
400 V class
Recommended wire
■
400 V class
Drive unit
Molded-case circuit breaker
Fuse (Class T)
Fuse (Class K5)
Frame, rated
current
Voltage AC [V]
Current [A]
Voltage AC [V]
Current [A]
Voltage AC [V]
MR-J5D_-_G_
30 A frame 5 A
480
1
600
1
600
Power regeneration converter unit
Semiconductor fuse (700 V)
SCCR 100 kA
(Manufactured by Eaton Bussman)
MR-CV11K4
170M1413 (40 A)
MR-CV18K4
170M1416 (80 A)
MR-CV30K4
170M1419 (160 A)
MR-CV37K4
170M1419 (160 A)
MR-CV45K4
170M1420 (200 A)
MR-CV55K4
170M1421 (250 A)
MR-CV75K4
170M1422 (315 A)
Drive unit
75 °C Stranded wire [AWG]
L11/L21/
U/V/W/E
MR-J5D1-100G4
14
14
MR-J5D1-200G4
MR-J5D1-350G4
MR-J5D1-500G4
12
MR-J5D1-700G4
10
MR-J5D2-100G4
14
MR-J5D2-200G4
MR-J5D2-350G4
MR-J5D2-500G4
12
MR-J5D2-700G4
10
MR-J5D3-100G4
14
MR-J5D3-200G4