7 - 14
7 Setting and procedure for operation
QE81WH4W
■
Extending the cable of 5 A current sensor
If the cable from current sensor is too short, you can extend it by using an extension cable as shown below.
Extension cable (standard)
Model name
EMU2-CB-T1M
EMU2-CB-T5M EMU2-CB-T10M
Cable length
1 m
5 m
10 m
Extension cable (separate)
Model name
EMU2-CB-T1MS
EMU2-CB-T5MS EMU2-CB-T10MS
Cable length
1 m
5 m
10 m
Connecting 5 A current sensor and the cable
◆Connecting 5 A current sensor and extension cable (standard)
◆Connecting 5 A current sensor and extension cable (separate)
EMU2-CT5-4W(0.5m)
EMU2-CB-T**MS(1~10m)
EMU2-CB-T**M(1~10m)
EMU2-CB-Q5A-4W(0.5m)
Not use
1)
Disconnect the connector of 1-phase and 3-phase. Keep connection of 2-phase.
2)
Connect the extension cable
EMU2-CB-T**MS(1~10m)
EMU2-CT5-4W(0.5m)
Supplementary
------------------------------------------------------------------------------------------------------------------------------
Cable extension for EMU2-CT5-4W is 10 m max. (Total cable length is 11m max.)
Not use
EMU2-CB-Q5A-4W(0.5m)
EMU2-CB-T**MS(1~10m)
Use extension cable (separate) when 1-phase, 2-phase and 3-phase are set apart.