8
Programming
QE81WH4W
(2) List of buffer memories to be used
Table 8.3-2 List of buffer memories to be used
Device
Description
Setting
value
Remarks
U0
\
G1
Input voltage
109
220 / 380 V
U0
\
G2
Primary current
3 250
A
U0
\
G3
Current demand time
30 30
sec
U0
\
G4
Electric power demand time
30 30
sec
U0
\
G5
Primary voltage of VT
0
When Primary voltage(U0¥G1)
is except 0
U0
\
G6
Secondary voltage of VT
0
When Primary voltage(U0\G1)
is except 0
U0
\
G7
Primary current of CT
0
When Primary current (U0\G2)
is except 0
U0
\
G11
Alarm 1 item
1
Current demand upper limit
U0
\
G12, 13
Alarm 1 value
100000 100
A
U0
\
G14
Alarm 1 reset method
1 Auto
reset
U0
\
G15
Alarm 1 delay time
5
5 sec
U0
\
G21
Alarm 2 item
1
Current demand upper limit
U0
\
G22, 23
Alarm 2 value
120000 120
A
U0
\
G24
Alarm 2 reset method
0 Self-retention
U0
\
G25
Alarm 2 delay time
5 5
sec
U0
\
G60, 61
Output period of data
acquisition clock
1000 1
sec
U0
\
G100
Multiplier of electric energy
-
Stores multiplier of electric
energy
U0
\
G102, 103
Electric energy (consumption)
-
Stores electric energy
U0
\
G218, 219
Average current
-
Stores average current
U0
\
G314, 315
Average value voltage (L-L)
-
Stores average value voltage
(L-L)
U0
\
G316, 317
Average value voltage (L-N)
-
Stores average value voltage
(L-N)
U0
\
G402, 403
Active energy
- Stores
active
energy
U0
\
G502, 503
Reactive power
-
Stores reactive power
U0
\
G602, 603
Apparent power
-
Stores apparent power
U0
\
G702, 703
Power factor
- Stores
power
factor
U0
\
G802, 803
Frequency
- Stores
frequency
U0
\
G3000
Latest error code
-
Stores latest error code
8 - 5