7 Setting and procedure for operation
QE81WH4W
7.6 Setting from GX Developer
This section explains setting from GX Developer necessary to use QE81WH4W. Before performing this
setting, install GX Developer and connect the Management CPU with the PC using a USB cable. For
details, refer to the manual of CPU module.
7.6.1 I/O assignment setting
(1) Double-click the dialog box of “PLC Parameter” in the GX Developer Project.
(2) Click “I/O assignment”.
(3) Set the following item to the slot*1 to which QE81WH4W has been attached.
Figure 7.6.1-1 Dialog box of “I/O assignment”
Table 7.6.1-1 Setting items on the “I/O assignment” tab
Item
Descriptions
Type
Select “Intelli.”.
Model name
Enter the model name of the module.
Points
Select 16 points.
Start XY
Enter the initial I/O number of QE81WH4W.
*1 is a case where QE81WH4W is attached to the slot 0.
7 - 16