8
Programming
QE81WH4W
8.2 System configuration and usage conditions for sample program
A sample program under the following system and the usage condition is shown below.
(1) System configuration
QY40 (Y20 to Y2F)
QCPU
QX40 (X10 to X1F)
QE81WH4W (X/Y0 to X/YF)
Figure 8.2-1 Sample system configuration using a sample program
(2) Setting conditions for the intelligent function of the module switch
Setting is as follows:
Table 8.2-1 Setting the intelligent function of the module switch
Switch No.
Switch name
Description
1 Not used
-
2 Not used
-
3 Not used
-
4 Not used
-
5 Test mode transition 0 (measuring mode)
(3) Programming conditions
(a) Setting the operating conditions
- Phase wire
: Three-phase 4-wire
- Input voltage
: 220 / 380 V
- Primary current
: 250 A
- Current demand time
: 30 sec
- Electric power demand time : 30 sec
-Primary voltage of VT
: 0
- Secondary voltage of VT : 0
- Primary current of CT : 0
(b) Alarm monitoring setting
- Alarm 1 item
: Current demand upper limit
- Alarm 1 value
: 100000 (100 A)
- Alarm 1 reset method
: Auto reset
- Alarm 1 delay time
: 5 sec
- Alarm 2 item
: Current demand upper limit
- Alarm 2 value
: 120000 (120 A)
- Alarm 2 reset method
: Self-retention
- Alarm 2 delay time
: 5 sec
8 - 2