7 - 15
7 Setting and procedure for operation
QE81WH4W
7.5.3.2 Voltage circuit connection
For the voltage circuit connection, there are two ways as follows:
1) Connect the voltage transform unit direct to the circuit.
2) Connect the voltage transform unit to voltage transformer secondary side.
In any case, circuit voltage can’t directly connect to voltage input terminal of QE81WH4W. Please
connect to voltage output terminal of voltage transform unit (QE8WH4VT).
If used at a circuit higher than 277/480V AC, make sure use a voltage transformer.
The transformer which has primary voltage of VT less than 6600V and secondary voltage of VT not
more than 220V can be used. Please connect the transformer secondary voltage to P1, P2, P3, and P0
terminals of QE8WH4VT. Make sure that terminal symbols are correct.
In order to perform maintenance work such as changing the wire layout and replacing equipment, we
recommend that you connect protective device (breaker or fuse) for the voltage input circuit of the
voltage transform unit (P1, P2, P3, and P0 terminals).
Breaker or fuse
P1
P2
P3
P0
Voltage transform unit
(
QE8WH4VT
)