햲
A FX
0N
-3A can not be connected to base units of the FX
3UC
series.
The Hardware
Extending for Special Functions
Training Manual GX IEC Developer
2 - 21
Combined
Analog
Input
&
O
utput
Modules
Temperature
A
cquisition
Modules
Analog
Output
Modules
Modul Type
Designation
No. of
channels
Range
Resolution
FX
1S
FX
1N
FX
2N
FX
2NC
FX
3G
FX
3U
FX
3UC
Special
Function
Modules
FX
2N
-4DA
4
Voltage:
-10 V to 10 V DC
5 mV
(with sign, 12 bits)
쑗
쎲
쎲
쎲
쎲
Current:
0 mA to 20 mA DC
4 mA to 20 mA DC
20 µA (10 Bit)
FX
3U
-4DA
4
Voltage:
-10 V to 10 V DC
0.32 mV
(with sign, 16 bits)
쑗
쑗
쑗
쎲
쎲
Current:
0 mA to 20 mA DC
4 mA to 20 mA DC
0.63 µA (15 Bit)
Special
Function
Modules
FX
0N
-3A
2 inputs
Voltage:
0 V to 5 V DC
0 V to 10 V DC
40 mV (8 Bit)
쑗
쎲
쎲
쑗
쎲
햲
Current:
4 mA to 20 mA DC
64 µA (8 Bit)
1 output
Voltage:
0 V to 5 V DC
0 V to 10 V DC
40 mV (8 Bit)
Current:
4 mA to 20 mA DC
64 µA (8 Bit)
FX
2N
-5A
4 inputs
Voltage:
-100 mV to 100 mV DC
-10 V to 10 V DC
50 µV
(with sign, 12 bits)
0.312 mV
(with sign, 16 bits)
쑗
쎲
쎲
쎲
쎲
Current:
4 mA to 20 mA DC
-20 mA to 20 mA DC
10 µA/1,25 µA
(with sign, 15 bits)
1 output
Voltage:
-10 V to 10 V DC
5 mV
(with sign, 12 bits)
Current:
0 mA to 20 mA DC
20 µA (10 Bit)
Special
Adapter
FX
3U
-3A-ADP
2 inputs
Voltage:
0 V to 10 V DC
2,5 mV (12 Bit)
쑗
쑗
쑗
쎲
쎲
Current:
4 mA to 20 mA DC
5 µA (12 Bit)
1 output
Voltage:
0 V to 10 V DC
2.5 mV (12 Bit)
Current:
4 mA to 20 mA DC
4 µA (12 Bit)
Special
Adapter
FX
3U
-4AD-PT-ADP
4
Pt100 resistance
thermometer:
-50
쎷
C to 250
쎷
C
0.1
쎷
C
쑗
쑗
쑗
쎲
쎲
FX
3U
-4AD-PTW-ADP
4
Pt100 resistance
thermometer:
-100
쎷
C to 600
쎷
C
0.2
쎷
C to 0.3
쎷
C
쑗
쑗
쑗
쎲
쎲
FX
3U
-4AD-PNK-ADP
4
Pt100 resistance
thermometer:
-50
쎷
C to 250
쎷
C
0.1
쎷
C
쑗
쑗
쑗
쎲
쎲
Ni1000 resistance
thermometer:
-40
쎷
C to110
쎷
C
0.1
쎷
C
쑗
쑗
쑗
쎲
쎲
FX
3U
-4AD-TC-ADP
4
Thermocouple type K:
-100
쎷
C to 1000
쎷
C
0.4
쎷
C
쑗
쑗
쑗
쎲
쎲
Thermocouple type J:
-100
쎷
C to 600
쎷
C
0.3
쎷
C
Summary of Contents for FX2N-32CAN
Page 1: ...MITSUBISHI ELECTRIC FACTORY AUTOMATION Programmable Logic Controllers GX IEC Developer ...
Page 2: ......
Page 4: ......
Page 6: ......
Page 10: ...IV MITSUBISHI ELECTRIC ...
Page 18: ...Modular PLC Training Hardware Course Overview and Requirements 1 2 MITSUBISHI ELECTRIC ...
Page 176: ...Device Edit 8 4 MITSUBISHI ELECTRIC ...
Page 190: ...Assigning DUT Variables to Function Blocks Data Unit Types DUT 10 10 MITSUBISHI ELECTRIC ...
Page 198: ...Array Example Single Dimension Array Arrays 11 8 MITSUBISHI ELECTRIC ...
Page 219: ...Sequential Function Chart SFC SFC Elements Training Manual GX IEC Developer 14 3 ...
Page 230: ...Structured Text Program Example IEC Structured Text 16 4 MITSUBISHI ELECTRIC ...
Page 278: ...PLC Components Glossary Appendix A 18 MITSUBISHI ELECTRIC ...
Page 283: ......