A.2.4
Error Codes (D8060 to D8069)
*
Cleared when PLC switches from STOP to RUN.
A.2.5
Extension Boards (Dedicated to FX
1S
and FX
1N
)
Special Registers
Appendix
A - 8
MITSUBISHI ELECTRIC
Special Register
Read
Write
CPU
Function
D8112
쏹
—
FX
1S
FX
1N
Adapter FX
1N
-2AD-BD: Digital input value ch.1
D8113
쏹
—
Adapter FX
1N
-2AD-BD: Digital input value ch.2
D8114
쏹
쏹
Adapter FX
1N
-1DA-BD: Digital output value ch.1
Special Register
Read
Write
CPU
Function
D8060
쏹
—
FX
2N
FX
2NC
FX
3G
FX
3U
FX
3UC
If the unit or block corresponding to a programmed I/O number
is not actually loaded, M8060 is set to ON and the first device
number of the erroneous block is written to D8060
Meaning of the four digit code:
1st digit: 0 = Output, 1 = Input
2nd to 4th digit: First device number of the erroneous block
D8061
쏹
—
FX
1S
FX
1N
FX
2N
FX
2NC
FX
3G
FX
3U
FX
3UC
Error code for PLC hardware error
D8062
쏹
—
FX
2N
,
FX
2NC
FX
3G
FX
3U
FX
3UC
Error code for PLC/PP communication error
FX
3G
Error code for serial communication error [ch0]
D8063
쏹
—
FX
1S
FX
1N
FX
2N
FX2NC
FX
3G
FX
3U
FX
3UC
Error code for serial communication error 1 [ch1]
D8064
쏹
—
Error code for parameter error
D8065
쏹
—
Error code for syntax error
D8066
쏹
—
Error code for ladder error
D8067
쏹
—
Error code for operation error
D8068*
—
쏹
Operation error step number latched
In case of 32K steps or more, the step number is stored in
[D8313, D8312].
D8069*
쏹
—
Error step number of M8065 to M8067
In case of 32K steps or more, the step number is stored in
[D8315, D8314].
Summary of Contents for FX2N-32CAN
Page 1: ...MITSUBISHI ELECTRIC FACTORY AUTOMATION Programmable Logic Controllers GX IEC Developer ...
Page 2: ......
Page 4: ......
Page 6: ......
Page 10: ...IV MITSUBISHI ELECTRIC ...
Page 18: ...Modular PLC Training Hardware Course Overview and Requirements 1 2 MITSUBISHI ELECTRIC ...
Page 176: ...Device Edit 8 4 MITSUBISHI ELECTRIC ...
Page 190: ...Assigning DUT Variables to Function Blocks Data Unit Types DUT 10 10 MITSUBISHI ELECTRIC ...
Page 198: ...Array Example Single Dimension Array Arrays 11 8 MITSUBISHI ELECTRIC ...
Page 219: ...Sequential Function Chart SFC SFC Elements Training Manual GX IEC Developer 14 3 ...
Page 230: ...Structured Text Program Example IEC Structured Text 16 4 MITSUBISHI ELECTRIC ...
Page 278: ...PLC Components Glossary Appendix A 18 MITSUBISHI ELECTRIC ...
Page 283: ......