29
GB
For PQHY-P·Y(S)LM-A1, PQHY-P·Y(S)LM-A2
<Additional Charge>
• Piping length from outdoor unit to the farthest indoor unit ≤ 30.5 m [100 ft]:
Use table [A].
• Piping length from outdoor unit to the farthest indoor unit > 30.5 m [100 ft]:
Use table [B].
Additional
refrigerant
charge
=
Liquid pipe size
Total length of
ø19.05 mm [3/4 in]
+
Liquid pipe size
Total length of
ø15.88 mm [5/8 in]
+
Liquid pipe size
Total length of
ø12.7 mm [1/2 in]
[A]
(kg)[oz]
[A]
(m) × 0.29 (kg/m)
(ft) × 3.12 (oz/ft)
[A]
(m) × 0.2 (kg/m)
(ft) × 2.16 (oz/ft)
[A]
(m) × 0.12 (kg/m)
(ft) × 1.30 (oz/ft)
[B]
(kg)[oz]
[B]
(m) × 0.26 (kg/m)
(ft) × 2.80 (oz/ft)
[B]
(m) × 0.18 (kg/m)
(ft) × 1.94 (oz/ft)
[B]
(m) × 0.11 (kg/m)
(ft) × 1.19 (oz/ft)
+
Liquid pipe size
Total length of
ø9.52 mm [3/8 in]
+
Liquid pipe size
Total length of
ø6.35 mm [1/4 in]
[A]
(m) × 0.06 (kg/m)
(ft) × 0.65 (oz/ft)
[A]
(m) × 0.024 (kg/m)
(ft) × 0.26 (oz/ft)
[B]
(m) × 0.054 (kg/m)
(ft) × 0.59 (oz/ft)
[B]
(m) × 0.021 (kg/m)
(ft) × 0.23 (oz/ft)
+
Additional charge
+
α
Heat source unit model
Charged amount
Single
P550
1.0 kg [36 oz]
P600
1.0 kg [36 oz]
<Example>
Indoor 1: 36 A: ø12.7 [1/2 in]
40 m [131 ft] a: ø9.52 [3/8 in]
10 m [32 ft]
At the
conditions
below:
2: 30
B: ø9.52 [3/8 in]
10 m [32 ft] b: ø9.52 [3/8 in]
5 m [16 ft]
3: 15
C: ø9.52 [3/8 in]
15 m [49 ft] c: ø6.35 [1/4 in]
10 m [32 ft]
4: 12 D: ø9.52 [3/8 in]
10 m [32 ft] d: ø6.35 [1/4 in]
10 m [32 ft]
5: 24
e: ø9.52 [3/8 in]
10 m [32 ft]
The total length of each liquid line is as follows:
ø12.7 [1/2 in]: A = 40 m [131 ft]
ø9.52 [3/8 in]: B + C + D + a + b + e = 10 [32] + 15 [49] + 10 [32] + 10 [32] + 5 [16]
+ 10 [32] = 60 m [193 ft]
ø6.35 [1/4 in]: c + d = 10 [32] + 10 [32] = 20 m [64 ft]
Therefore, additional refrigerant charge
= 40 m [131 ft] × 0.11 kg/m [1.19 oz/ft] + 60 m [193 ft] × 0.054 kg/m [0.59 oz/ft]
+ 20 m [64 ft] × 0.021 kg/m [0.23 oz/ft] + 3.0 kg [106 oz] = 11.1 kg [391 oz]
Value of α
Total capacity of connected indoor units
α
80 or below
2.0 kg [71 oz]
81 to 160
2.5 kg [89 oz]
161 to 330
3.0 kg [106 oz]
331 to 390
3.5 kg [124 oz]
391 to 480
4.5 kg [159 oz]
481 to 630
5.0 kg [177 oz]
631 to 710
6.0 kg [212 oz]
711 to 800
8.0 kg [283 oz]
801 to 890
9.0 kg [318 oz]
891 to 1070
10.0 kg [353 oz]
1071 to 1250
12.0 kg [424 oz]
1251 or above
14.0 kg [494 oz]
Note:
For PQHY/PQRY-P·Y(S)LM-A1, PQHY/PQRY-P·Y(S)LM-A2
* When connecting PEFY-P20VMA3-E units, add 0.54 kg of refrigerant for
each of these units.
* When connecting PEFY-P25/32/40VMA3-E units, add 0.74 kg of refrigerant
for each of these units.
* When connecting PEFY-P50/63/71/80/100/125VMA3-E units, add 1.16 kg
of refrigerant for each of these units.
For PQRY-P·Y(S)LM-A1, PQRY-P·Y(S)LM-A2
<Additional charge>
• Piping length from outdoor unit to the farthest indoor unit ≤ 30.5 m [100 ft]:
Use table [A].
• Piping length from outdoor unit to the farthest indoor unit > 30.5 m [100 ft]:
Use table [B].
Additional
refrigerant
charge
=
High-pressure
pipe size
Total length of
ø28.58 mm [1-1/8 in]
+
High-pressure
pipe size
Total length of
ø22.2 mm [7/8 in]
+
High-pressure
pipe size
Total length of
ø19.05 mm [3/4 in]
[A]
(kg)[oz]
[A]
(m) × 0.36 (kg/m)
(ft) × 3.88 (oz/ft)
[A]
(m) × 0.23 (kg/m)
(ft) × 2.48 (oz/ft)
[A]
(m) × 0.16 (kg/m)
(ft) × 1.73 (oz/ft)
[B]
(kg)[oz]
[B]
(m) × 0.33 (kg/m)
(ft) × 3.55 (oz/ft)
[B]
(m) × 0.21 (kg/m)
(ft) × 2.26 (oz/ft)
[B]
(m) × 0.14 (kg/m)
(ft) × 1.51 (oz/ft)
+
High-pressure
pipe size
Total length of
ø15.88 mm [5/8 in]
+
Liquid Piping Size
Total length of
ø15.88 mm [5/8 in]
+
Liquid Piping Size
Total length of
ø12.7 mm [1/2 in]
[A]
(m) × 0.11 (kg/m)
(ft) × 1.19 (oz/ft)
[A]
(m) × 0.2 (kg/m)
(ft) × 2.16 (oz/ft)
[A]
(m) × 0.12 (kg/m)
(ft) × 1.30 (oz/ft)
[B]
(m) × 0.1 (kg/m)
(ft) × 1.08 (oz/ft)
[B]
(m) × 0.18 (kg/m)
(ft) × 1.94 (oz/ft)
[B]
(m) × 0.11 (kg/m)
(ft) × 1.19 (oz/ft)
+
Liquid Piping Size
Total length of
ø9.52 mm [3/8 in]
+
Liquid Piping Size
Total length of
ø6.35 mm [1/4 in]
[A]
(m) × 0.06 (kg/m)
(ft) × 0.65 (oz/ft)
[A]
(m) × 0.024 (kg/m)
(ft) × 0.26 (oz/ft)
[B]
(m) × 0.054 (kg/m)
(ft) × 0.59 (oz/ft)
[B]
(m) × 0.021 (kg/m)
(ft) × 0.23 (oz/ft)
+
Additional charge
+
HBC controller
(CMB-WP108/
1016V-GA1)
Heat source unit model
Charged amount
Single
P550
1.0 kg [36 oz]
3.0 kg [106 oz]
P600
1.0 kg [36 oz]
+
BC controller
(Standard/Main)
+
BC controller
(Main) HA-Type
3.0 kg [106 oz]
2.0 kg [71 oz]
+
BC controller
(Sub) Total Units
BC controller
(Sub) Per Unit
1
1.0 kg [36 oz]
2
2.0 kg [71 oz]
+
Total capacity of
connected indoor units
Amount
(to be added for indoor units)
80 or below
2.0 kg [71 oz]
81 to 160
2.5 kg [89 oz]
161 to 330
3.0 kg [106 oz]
331 to 390
3.5 kg [124 oz]
391 to 480
4.5 kg [159 oz]
481 to 630
5.0 kg [177 oz]
631 to 710
6.0 kg [212 oz]
711 to 800
8.0 kg [283 oz]
801 to 890
9.0 kg [318 oz]
891 to 1070
10.0 kg [353 oz]
1071 to 1250
12.0 kg [424 oz]
1251 or above
14.0 kg [494 oz]
* For Hybrid City Multi system, the refrigerant charge amount
for indoor units is excluded.
<Example>
Indoor
1: 30
A: ø28.58 [1-1/8 in] 40 m [131 ft] a: ø9.52 [3/8 in]
10 m [32 ft]
At the
conditions
below:
2: 96 B: ø9.52 [3/8 in]
10 m [32 ft] b: ø9.52 [3/8 in]
5 m [16 ft]
3: 12
C: ø9.52 [3/8 in]
20 m [64 ft] c: ø6.35 [1/4 in]
5 m [16 ft]
4: 15 D: ø9.52 [3/8 in]
5 m [16 ft]
d: ø6.35 [1/4 in]
10 m [32 ft]
5: 12
E: ø9.52 [3/8 in]
5 m [16 ft]
e: ø6.35 [1/4 in]
5 m [16 ft]
6: 24 F: ø22.2 [7/8 in]
3 m [9 ft]
f: ø9.52 [3/8 in]
5 m [16 ft]
G: ø19.05 [3/4 in]
1 m [3 ft]
The total length of each liquid line is as follows:
ø28.58 [1-1/8 in]: A = 40 m [131 ft]
ø22.2 [7/8 in]: F = 3 m [9 ft]
ø19.05 [3/4 in]: G = 1 m [3 ft]
ø9.52 [3/8 in]: C + D + E + a + b + f = 50 m [164 ft]
ø6.35 [1/4 in]: c + d + e = 20 m [64 ft]
Therefore, additional refrigerant charge
= 40 m [131 ft] × 0.33 kg/m [3.55 oz/ft] + 3 m [9 ft] × 0.21 kg/m [2.26 oz/ft]
+ 1 [3 ft] × 0.14 kg/m [1.51 oz/ft] + 50 m [164 ft] × 0.054 kg/m [0.59 oz/ft]
+ 20 m [64 ft] × 0.021 kg/m [0.23 oz/ft] + 3.0 kg [106 oz] + 2.0 kg [71 oz]
+ 5.0 kg [177 oz]
= 27.1 kg [956 oz]