18
WIRING
l
Three-phase 400 V class (440 V input power supply, with a power factor improving AC or DC reactor)
For footnotes *1 to *4 refer to next page.
l
Single-phase 200 V class (220 V input power supply, without a power factor improving AC or DC reactor)
l
Single-phase 200 V class (220 V input power supply, with a power factor improving AC or DC reactor)
*1
The cable size is that of the HIV cable (600 V grade heat-resistant PVC insulated wire) etc. with continuous maximum permissible
temperature of 75°C. It assumes a surrounding air temperature of 50°C or lower and the wiring distance of 20 m or shorter.
*2
The cable size is that of the THHW cable with continuous maximum permissible temperature of 75°C. It assumes a surrounding air
temperature of 40°C or lower and the wiring distance of 20 m or shorter.
(For the use in the United States or Canada, refer to "Instructions for UL and cUL" in the document enclosed with the product.)
*3
The cable size is that of the PVC cable with continuous maximum permissible temperature of 70°C. It assumes a surrounding air
temperature of 40°C or lower and the wiring distance of 20 m or shorter.
(Selection example mainly for use in Europe.)
*4
The screw size for terminals R/L1, S/L2, T/L3, U, V, W, PR, P/+, N/-, and P1, and the earthing (grounding) terminal is shown.
The screw size for earthing (grounding) the FR-E820-0600(15K) to FR-E820-0900(22K) is indicated in parentheses.
Applicable
inverter type
FR-E840-
ã
Terminal
screw
size
*4
Tightening
torque
[Nm]
Crimping
terminal
Cable sizes
HIV, etc. [mm²]
*1
AWG/MCM
*2
PVC, etc. [mm²]
*3
R/L1,
S/L2,
T/L3
U, V, W
R/L1,
S/L2,
T/L3
U, V, W P/+, P1
Earth
cable
gauge
R/L1,
S/L2,
T/L3
U, V, W
R/L1,
S/L2,
T/L3
U, V, W
Earth
cable
gauge
0016(0.4K) to
0095(3.7K)
M4
1.5
2–4
2–4
2
2
2
2
14
14
2.5
2.5
2.5
0120(5.5K)
M4
1.5
2–4
2–4
2
2
3.5
2
14
14
2.5
2.5
2.5
0170(7.5K)
M4
1.5
5.5–4
5.5–4
3.5
3.5
3.5
3.5
12
12
4
4
4
0230(11K)
M4
1.5
5.5–4
5.5–4
5.5
5.5
5.5
5.5
10
10
6
6
6
0300(15K)
M5
2.5
8–5
8–5
8
8
8
5.5
8
8
10
10
10
0380(18.5K)
M6
4.4
8–6
8–6
8
8
14
8
8
8
10
10
10
0440(22K)
M6
4.4
14–6
14–6
14
14
22
14
6
6
16
16
16
Applicable
inverter type
FR-E820S-
ã
Terminal
screw
size
*4
Tightening
torque
[Nm]
Crimping
terminal
Cable sizes
HIV, etc. [mm²]
*1
AWG/MCM
*2
PVC, etc. [mm²]
*3
R/L1,
S/L2,
T/L3
U, V, W
R/L1,
S/L2,
T/L3
U, V, W P/+, P1
Earth
cable
gauge
R/L1,
S/L2,
T/L3
U, V, W
R/L1,
S/L2,
T/L3
U, V, W
Earth
cable
gauge
0008(0.1K) to
0030(0.4K)
M3.5
1.2
2–3.5
2–3.5
2
2
2
2
14
14
2.5
2.5
2.5
0050(0.75K),
0080(1.5K)
M4
1.5
2–4
2–4
2
2
2
2
14
14
2.5
2.5
2.5
0110(2.2K)
M4
1.5
5.5–4
2–4
3.5
2
2
2
12
14
4
2.5
2.5
Applicable
inverter type
FR-E820S-
ã
Terminal
screw
size
*4
Tightening
torque
[Nm]
Crimping
terminal
Cable sizes
HIV, etc. [mm²]
*1
AWG/MCM
*2
PVC, etc. [mm²]
*3
R/L1,
S/L2,
T/L3
U, V, W
R/L1,
S/L2,
T/L3
U, V, W P/+, P1
Earth
cable
gauge
R/L1,
S/L2,
T/L3
U, V, W
R/L1,
S/L2,
T/L3
U, V, W
Earth
cable
gauge
0008(0.1K) to
0030(0.4K)
M3.5
1.2
2–3.5
2–3.5
2
2
2
2
14
14
2.5
2.5
2.5
0050(0.75K),
0080(1.5K)
M4
1.5
2–4
2–4
2
2
2
2
14
14
2.5
2.5
2.5
0110(2.2K)
M4
1.5
5.5–4
2–4
3.5
2
2
2
12
14
4
2.5
2.5
Summary of Contents for 800 Series
Page 10: ...4 INSTALLATION AND INSTRUCTIONS ...
Page 46: ...40 BASIC OPERATION ...
Page 64: ...58 INVERTER FAULT AND ALARM INDICATIONS ...
Page 70: ...64 SPECIFICATIONS ...