WIRING
l
Single-phase 200 V class
l
Handling of the wiring cover
(FR-E820-0470(11K) to 0900(22K), FR-E840-0230(11K) to 0440(22K))
For the hook of the wiring cover, cut off the necessary parts using a pair of needle-nose pliers etc.
FR-E820S-0008(0.1K) to 0030(0.4K)
FR-E820S-0050(0.75K) to 0110(2.2K)
CAUTION
l
The power supply cables must be connected to R/L1, S/L2, T/L3. Never connect the power cable to the U, V, W, of the inverter. Doing
so will damage the inverter. (Phase sequence needs not to be matched.)
l
Connect the motor to U, V, W. At this time turning on the forward rotation switch (signal) rotates the motor in the clockwise direction
when viewed from the motor shaft. (The phase sequence must be matched.)
CAUTION
l
Cut off the same number of lugs as wires. If parts where no wire is put through have been cut off (10 mm or more), protective structure
(IEC 60529) becomes an open type (IP00).
N/-
P/+
PR
R/L1
S/L2
M
Motor
Power supply
Jumper
Earthing (grounding)
terminal
Jumper
N/- P/+
PR
R/L1 S/L2
M
Earthing (grounding)
terminal
Jumper
Motor
Power supply