66
APPENDIX
A.1.2 Low Voltage Directive
We have self-confirmed our inverters as products compliant to the Low Voltage Directive 2014/35/EU (conforming stand-
ard EN 61800-5-1) and place the CE mark on the inverters.
Outline of instructions
l
Do not use an earth leakage current breaker as an electric shock protector without connecting the equipment to the
earth. Connect the equipment to the earth securely.
l
Wire the earth terminal independently. (Do not connect two or more cables to one terminal.)
l
Use the cable sizes on
under the following conditions.
– Surrounding air temperature: 40°C maximum
If conditions are different from above, select appropriate wire according to EN60204 Appendix C TABLE 5.
l
Use a tinned (plating should not include zinc) crimping terminal to connect the earth cable. When tightening the screw,
be careful not to damage the threads.
For use as a product compliant with the Low Voltage Directive, use PVC cable whose size is indicated on
l
Use the moulded case circuit breaker and magnetic contactor which conform to the EN or IEC Standard.
l
This product can cause a DC current in the protective earthing conductor. Where a residual current-operated protective
(RCD) or monitoring (RCM) device is used for protection in case of direct or indirect contact, only an RCD or RCM of
Type B is allowed on the supply side of this product.
l
Use the inverter under the conditions of overvoltage category III specified in IEC 60664.
l
To use the inverter under the conditions of pollution degree 3, install it in the enclosure of IP54 or higher.
If the cover is not fixed, the inverter protective structure is regarded as IP00.
Fan cover
Fan
FR-E820-0080(1.5K) to 0330(7.5K)
FR-E840-0040(1.5K) to 0170(7.5K)
FR-E860-0027(1.5K) to 0120(7.5K)
FR-E820S-0080(1.5K) to 0110(2.2K)
Fan cover
Fan
FR-E820-0470(11K) to 0900(22K)
FR-E840-0230(11K) to 0440(22K)