17
WIRING
2.3 Wiring fundamentals
2.3.1 Applicable cables and wiring length
For the ND rating
l
Three-phase 200 V class (220 V input power supply, without a power factor improving AC or DC reactor)
l
Three-phase 200 V class (220 V input power supply, with a power factor improving AC or DC reactor)
l
Three-phase 400 V class (440 V input power supply, without a power factor improving AC or DC reactor)
Applicable
inverter type
FR-E820-
ã
Terminal
screw
size
*4
Tightening
torque
[Nm]
Crimping
Terminal
Cable sizes
HIV, etc. [mm²]
*1
AWG/MCM
*2
PVC, etc. [mm²]
*3
R/L1,
S/L2,
T/L3
U, V, W
R/L1,
S/L2,
T/L3
U, V, W P/+, P1
Earth
cable
gauge
R/L1,
S/L2,
T/L3
U, V, W
R/L1,
S/L2,
T/L3
U, V, W
Earth
cable
gauge
0008(0.1K) to
0050(0.75K)
M3.5
1.2
2–3.5
2–3.5
2
2
2
2
14
14
2.5
2.5
2.5
0080(1.5K),
0110(2.2K)
M4
1.5
2–4
2–4
2
2
2
2
14
14
2.5
2.5
2.5
0175(3.7K)
M4
1.5
5.5–4
5.5–4
3.5
3.5
3.5
3.5
12
12
4
4
4
0240(5.5K)
M5
2.5
5.5–5
5.5–5
5.5
5.5
5.5
5.5
10
10
6
6
6
0330(7.5K)
M5
2.5
14–5
8–5
14
8
8
5.5
6
8
16
10
6
0470(11K)
M5
2.5
14-5
14-5
14
14
14
8
6
6
16
16
16
0600(15K)
M6 (M5)
4.4
22-6
22-6
22
22
22
14
4
4
25
25
16
0760(18.5K)
M8 (M6)
7.8
38-8
22-8
38
22
38
14
2
2
35
25
25
0900(22K)
M8 (M6)
7.8
38-8
38-8
38
38
38
22
2
2
35
35
25
Applicable
inverter type
FR-E820-
ã
Terminal
screw
size
*4
Tightening
torque
[Nm]
Crimping
Terminal
Cable sizes
HIV, etc. [mm²]
*1
AWG/MCM
*2
PVC, etc. [mm²]
*3
R/L1,
S/L2,
T/L3
U, V, W
R/L1,
S/L2,
T/L3
U, V, W P/+, P1
Earth
cable
gauge
R/L1,
S/L2,
T/L3
U, V, W
R/L1,
S/L2,
T/L3
U, V, W
Earth
cable
gauge
0008(0.1K) to
0050(0.75K)
M3.5
1.2
2–3.5
2–3.5
2
2
2
2
14
14
2.5
2.5
2.5
0080(1.5K),
0110(2.2K)
M4
1.5
2–4
2–4
2
2
2
2
14
14
2.5
2.5
2.5
0175(3.7K)
M4
1.5
5.5–4
5.5–4
3.5
3.5
3.5
3.5
12
12
4
4
4
0240(5.5K)
M5
2.5
5.5–5
5.5–5
5.5
5.5
5.5
5.5
10
10
6
6
6
0330(7.5K)
M5
2.5
8–5
8–5
8
8
8
5.5
8
8
10
10
6
0470(11K)
M5
2.5
14–5
14–5
14
14
14
8
6
6
16
16
16
0600(15K)
M6 (M5)
4.4
22–6
22–6
22
22
22
14
4
4
25
25
16
0760(18.5K)
M8 (M6)
7.8
22–8
22–8
22
22
38
14
4
2
25
25
25
0900(22K)
M8 (M6)
7.8
38–8
38–8
38
38
38
22
2
2
35
35
25
Applicable
inverter type
FR-E840-
ã
Terminal
screw
size
*4
Tightening
torque
[Nm]
Crimping
terminal
Cable sizes
HIV, etc. [mm²]
*1
AWG/MCM
*2
PVC, etc. [mm²]
*3
R/L1,
S/L2,
T/L3
U, V, W
R/L1,
S/L2,
T/L3
U, V, W P/+, P1
Earth
cable
gauge
R/L1,
S/L2,
T/L3
U, V, W
R/L1,
S/L2,
T/L3
U, V, W
Earth
cable
gauge
0016(0.4K) to
0095(3.7K)
M4
1.5
2–4
2–4
2
2
2
2
14
14
2.5
2.5
2.5
0120(5.5K)
M4
1.5
5.5–4
2–4
3.5
2
3.5
3.5
12
14
4
2.5
4
0170(7.5K)
M4
1.5
5.5–4
5.5–4
3.5
3.5
3.5
3.5
12
12
4
4
4
0230(11K)
M4
1.5
5.5–4
5.5–4
5.5
5.5
5.5
5.5
10
10
6
6
10
0300(15K)
M5
2.5
8–5
8–5
8
8
8
5.5
8
8
10
10
10
0380(18.5K)
M6
4.4
14–6
8–6
14
8
14
8
6
6
16
10
16
0440(22K)
M6
4.4
14–6
14–6
14
14
22
14
6
6
16
16
16
Summary of Contents for 800 Series
Page 10: ...4 INSTALLATION AND INSTRUCTIONS ...
Page 46: ...40 BASIC OPERATION ...
Page 64: ...58 INVERTER FAULT AND ALARM INDICATIONS ...
Page 70: ...64 SPECIFICATIONS ...