50
PARAMETER LIST
834
Torque control P
gain 2 (current loop
proportional gain)
0% to 500%,
9999
9999
835
Torque control
integral time 2
(current loop integral
time)
0 to 500 ms,
9999
9999
836
Torque setting filter 2
0 to 5 s, 9999
9999
840
Torque bias selection
0 to 3, 9999
9999
841
Torque bias 1
600% to 1400%,
9999
9999
842
Torque bias 2
600% to 1400%,
9999
9999
843
Torque bias 3
600% to 1400%,
9999
9999
844
Torque bias filter
0 to 5 s, 9999
9999
845
Torque bias operation
time
0 to 5 s, 9999
9999
846
Torque bias balance
compensation
0% to 100%,
9999
9999
847
Fall-time torque bias
terminal 4 bias
0% to 400%,
9999
9999
848
Fall-time torque bias
terminal 4 gain
0% to 400%,
9999
9999
849
Analog input offset
adjustment
0% to 200%
100%
850
Brake operation
selection
0 to 2
0
853
Speed deviation time
0 to 100 s
1 s
854
Excitation ratio
0% to 100%
100%
858
Terminal 4 function
assignment
0, 4, 6, 9999
0
859
Torque current/Rated
PM motor current
0 to 500 A, 9999
9999
860
Second motor torque
current/Rated PM
motor current
0 to 500 A, 9999
9999
864
Torque detection
0% to 400%
150%
865
Low speed detection
0 to 590 Hz
1.5 Hz
866
Torque monitoring
reference
0% to 400%
150%
867
AM output filter
[E800-4][E800-5]
0 to 5 s
0.01 s
870
Speed detection
hysteresis
0 to 15 Hz
0 Hz
872
Input phase loss
protection selection
[3-phase]
0, 1
1
873
*4
Speed limit
0 to 400 Hz
20 Hz
874
OLT level setting
0% to 400%
150%
877
Speed feed forward
control/model
adaptive speed
control selection
0 to 2
0
878
Speed feed forward
filter
0.01 to 1 s
0.01 s
879
Speed feed forward
torque limit
0% to 400%
150%
880
Load inertia ratio
0 to 200 times
7 times
881
Speed feed forward
gain
0% to 1000%
0%
Para-
meter
Name
Setting Range
Initial
Value
*1
882
Regeneration
avoidance operation
selection
0 to 2
0
883
Regeneration
avoidance operation
level
300 to 1200 V
[200 V class]
400 V
[400 V class]
780 V
[575 V class]
944 V
885
Regeneration
avoidance
compensation
frequency limit value
0 to 45 Hz, 9999 6 Hz
886
Regeneration
avoidance voltage
gain
0% to 200%
100%
888
Free parameter 1
0 to 9999
9999
889
Free parameter 2
0 to 9999
9999
891
Cumulative power
monitor digit shifted
times
0 to 4, 9999
9999
892
Load factor
30% to 150%
100%
893
Energy saving
monitor reference
(motor capacity)
0.1 to 30 kW
Inverter
rated
capacity
894
Control selection
during commercial
power-supply
operation
0 to 3
0
895
Power saving rate
reference value
0, 1, 9999
9999
896
Power unit cost
0 to 500, 9999
9999
897
Power saving
monitor average time
0 to 1000 h,
9999
9999
898
Power saving
cumulative monitor
clear
0, 1, 10, 9999
9999
899
Operation time rate
(estimated value)
0% to 100%,
9999
9999
986
Display safety fault
code [E800-SCE]
0 to 127
0
990
PU buzzer control
0, 1
1
991
PU contrast
adjustment
0 to 63
58
992
Operation panel
setting dial push
monitor selection
[E800]
0 to 3, 5 to 14,
17 to 20, 23 to
33, 35, 38, 40 to
42, 44, 45, 50 to
57, 61, 62, 64,
65, 67, 91,
97, 100
0
997
Fault initiation
0 to 255, 9999
9999
998
PM parameter
initialization
0, 8009, 8109,
9009, 9109,
0
999
Automatic parameter
setting
10, 12, 20, 21,
9999
9999
Parameter 1000 to 1099
Para-
meter
Name
Setting Range
Initial
Value
*1
1002
Lq tuning target
current adjustment
coefficient
50% to 150%,
9999
9999
1006
Clock (year)
2000 to 2099
2000
Para-
meter
Name
Setting Range
Initial
Value
*1
Simple
Simple
Simple
Simple
Simple
Simple