BPS-1100 Installation and Operation Manual
1
1.0 Introduction
Mircom's BPS-1100 Signal Booster Power Supply provides up to 20 fully supervised Class A or B (UL Style Z or Y)
Indicating Circuits. All Indicating Circuits are fully supervised for opens, shorts and grounds. Optional Adder
Modules include additional Indicating Circuits and Relay Circuits. Flush or surface mountable enclosures can be
used for retrofits and on new installations.
1.1 Overall Features:
• 120V/240V AC, 24V DC, 11 Amps Max
• Basic unit has 4 Power Limited Class A/B (Style Z/Y) Indicating Circuits with individual trouble indicators (1.7A
Max per circuit).
• 4 supervised programmable inputs
• Optional 3 Adder Modules for additional Indicating and Relay Circuits. Indicating Circuits expandable by 16
(with 3 SGM-1004As) and Relay Circuits by 16 (with 2 RM-1008As).
• Supports supervised and unsupervised suite isolators
• Regulated Auxiliary Output 24V DC, 1.7A
• Space for 10 to 17 Amp Hour Batteries
• Each Indicator Circuit can be configured as Audible or Visual. Audibles may be steady, Temporal Code,
California Code, or March Time.
• Indicating Circuits may be individually Disconnected by a DIP Switch.
• Two outputs (200 mA each Max., 300 mA total Max.)
• Auxiliary Relay Contacts for Common Ground and Common Trouble.
• Easy Configuration via Pushbuttons and Switches.
• Extensive transient protection
• Surface Mountable Enclosures, Flush Trims Available
1.2 Controls and Indicators
4 Pushbuttons, 7 Common Indicators, provision for up to 4 Inputs and 20 Output Points.