Appendix A - Module Specifications And Features
30
Appendix A - Module Specifications And Features
Main Chassis
Signal Adder Module (SGM-1004A)
General
4 supervised Style B
(Class B) Initiating Circuits; fully
configurable. Terminals are labelled “INI”.
Power limited:
22 VD, 3mA standby, 5mV ripple, 50mA
max. (alarm)
4 Style Y or Z
(Class B or A) Indicating Circuits;
configurable as strobes or audibles. Terminals are labelled
“IND”.
Power limited:
24 VDC unfiltered
1.7 A @ 49E C per Circuit
Up to
3 Circuit Adders may
be added.
Displays and Disconnect Switches
for up to 24 Circuits. 4
Inputs & 20 Outputs
Aux. Power Supply
. Terminals are labelled "AUX PWR".
Power limited:
24 VDC Filtered
1.7 A @ 49E C
Two Power Supplies.
Terminals are labelled “4-WIRE”.
Power limited:
22 VDC, 200 mA each max., 300 mA total
max, 5 mV ripple
Auxiliary relays:
(resistive loads)
Must be connected to a Listed Power Limited Source of
Supply. Terminals are labelled “GROUND” and “TROUBLE”.
Common Ground: Form C, 1 Amp, 28 VDC
Common Trouble: Form C, 1 Amp, 28 VDC
Micro-controller based design.
Fully Configurable from Front Panel.
Full walk test function.
Electrical Ratings
AC Line Voltage:
120V 60Hz / 240V, 50Hz
2 Amps / 1 Amp (primary)
Power Supply ratings:
12 Amps. max. (secondary)
For Indicating Circuits:
24VDC unfiltered, Power Limited
11 Amps. max. (6.0 Amps for main
board fully loaded)
Battery:
24VDC, Gel-Cell/Sealed Lead-Acid
Charging capability:
10-17 AH batteries
Current Consumption:
standby: 200 mA
alarm: 350 mA
4 Style Y or Z (Class B or A) Indicating Circuits; configurable
as strobes or audibles (NOT synchronized). Terminals are
labelled “IND”.
Power limited:
24 VDC unfiltered
Max. 1.7 A @ 49° C per Circuit
Current Consumption:
standby:
35 mA
alarm: 150
mA
Relay Adder Module (RM-1008A) (resistive loads)
Must be connected to a Listed Power Limited Source of
Supply. Terminals are labelled “RLY”.
8 fully Configurable
Form C Relays
.
Form C, 1 Amp., 28 VDC (resistive loads)
Current Consumption:
standby:
25 mA
alarm: 150
mA
Compliance
System Model:
BPS-1100 Signal Booster Power Supply
Applicable Standards:
NFPA 72, ULC-S527-99, ULC-S525, ULC-526, ULC-S318