6.0 Module Settings
6.1 Main Chassis Board of the BPS-1100
JW6
This Continuity Jumper is removed if there are any Adder Modules (Signal and Relay) installed, and
installed on the last Adder Module.
W1
Cut this jumper to disable ground fault detection on the BPS-1100. Therefore, there will be no ground fault
detection other than from the Fire Alarm Panel.
P3
Connector for front Display Module (part of MCC-1100).
P5
Connector for Adder Modules.
P6
Power Connector for Adder Modules.
P7,8
Factory connection to Bridge Rectifier.
P9,10
Connection to 24 VDC Battery.
F1
20 Amp 1.25" Fast Blow Battery Charge Fuse
Figure 5: Main Chassis board of the BPS-1100