7.0 Field Wiring
14
Figure 10: Main BPS-1100 Module Terminal Connections (continued)
Note:
All power limited circuits must use type FPL, FPLR, or FPLP power limited cable
Initiating Circuits
are fully supervised and rated for 22 VDC, 3mA standby, 5 mV ripple, 50mA max.
alarm. They may be configured as required. The alarm threshold is 21mA. Maximum loop resistance
is 100 ohms, 50 ohms per side.
Indicating Circuits
are fully supervised and rated for 24 VDC unfiltered 1.7 amp Max. They must be
wired as shown in the wiring tables.
INPUT 1 (POWER LIMITED)
INPUT 2 (POWER LIMITED)
INPUT 3 (POWER LIMITED)
INPUT 4 (POWER LIMITED)
N.C.
N.O.
N.C.
N.O.
N.C.
N.O.
N.C.
N.O.