81
13. I/O Test Screen
This screen is used to check external control input and output.
You can check the start trigger signal input, alarm resetting signal input, and alarm output signal
output.
It is useful for checking whether external control devices are connected or disconnected, and for
checking the operation of the module.
(1) Input
Falling pulse to the start trigger input (IN1-COM1)* [IN 1] illuminates for 3 seconds on each pulse.
Falling pulse to the alarm resetting input (IN2-COM2)* [IN 2] illuminates for 3 seconds on each pulse.
* Minimum pulse width: 1 ms
(2) Output
Clicking [ON] short-circuits the alarm output (OUT-COM3).
The alarm LED on the module also illuminates.
* The analog output voltage is 0 V for all channels while the I/O Test screen is displayed.