MP 26/10
Installation and Calibration Manual
Minebea Intec
EN-8
2.4.
Connecting outputs OUT1 / OUT2
Two digital outputs can be set from the device. The outputs are
activated according to the configuration and parameter settings.
The relay outputs should be max. 250V/2A.
No
contact should exist between common terminals.
OUT1 ports: 17, 18
OUT2 ports: 17, 14
Note:
If relays OUT1, 2 and 3 are used to operate external contactors, these must be fitted with RC snubber circuits
according to manufacturer specifications to prevent excessive voltage peaks at switch-off.
Contact type:
2 normally open relay outputs with common
contact connections (galvanic insulation is
provided between inputs and outputs )
Max. contact rating: 500 VA, max. 250 V, max. 2A at 48...62 Hz,
ohmic load
Min. contact rating:
6 V, 1 mA DC
Switching cycles
(electrical)
for I = 1 A/2 A:
>
800,000/500,000 (at~250V (ohmic load)