Click the 'SAVE' button to write the settings to the GridTime 3000.
A 'Saved!' notification will appear in the bottom right corner of the page indicating that the settings have
successfully been written to the GridTime 3000.
9.5.7.3
C37.238-2011 Power Profile
This section describes how to provision a GridTime 3000 with the C37.238-2011 Power Profile.
1.
Select C37.238-2011 Power Profile
Select 'C37.238-2011 Power Profile' from the 'PTP PROFILE' dropdown.
2.
Follow the instructions in one of the following sections depending on your desired PTP Clock Mode:
–
9.5.7.3.1. C37.238-2011 Power Profile Auto Mode
–
9.5.7.3.2. C37.238-2011 Power Profile Server Only Mode
–
9.5.7.3.3. C37.238-2011 Power Profile Client Only Mode
PTP Clock Mode Descriptions
Auto mode allows the port to operate either in the server or client state depending on whether the GridTime 3000 is
synchronized or not. When the GridTime 3000 is in sync or in holdover, the port will be in the server or passive server
state, when the GridTime 3000 is out of sync the port will be in the client state.
In server only mode, the port will always either be in the server or passive server state depending on whether it has
won the BMCA or not.
In client only mode, the port will always be in the client or listening state depending on whether there is a PTP server
available to sync to.
9.5.7.3.1 C37.238-2011 Power Profile Auto Mode
This section describes how to provision a PTP C37.238-2011 Power Profile Auto Mode Clock.
1.
Select Auto for PTP Clock Mode
Select 'Auto' from the 'PTP CLOCK MODE' dropdown.
Provisioning
©
2022 Microchip Technology Inc.
and its subsidiaries
Manual
DS00004572A-page 113