Important notices
•
To determine the limits in the programmed mode, it is
essential to execute the
cal
or
ncal
procedure first,
because this procedure clears the position counter and the
limit registers.
•
The velocities to execute the limit switch movements has
to be chosen very carefully because:
The motors are interrupted immediately if the limit-
switches are activated, this causes a back electromotive
force (bemf) that can reset the controller
To much speed can bring the axis in collision with the
the mechanical limits.
To achieve a good repeatability of the determined limit
coordinates, especially the velocity for moving out of the
limit-switches should be chosen as small as possible.
•
The broadcast limit switch teach-in procedure blocks the
Venus-1 interpreter for all other commands except Ctrl+c.
•
For safety reasons the determined limits can not be stored
permanently.
•
Software limits can be defined additionally. See command
setnlimit
.
Summary of Contents for Corvus ECO
Page 1: ...Version 1 0 Manual Corvus eco high resolution positioning controller...
Page 5: ...Manual Corvus eco Content 5...
Page 8: ...Chapter 1 Manual Corvus eco Introduction 8 Introduction...
Page 13: ...Chapter 2 Manual Corvus eco Starting up 13 Starting up...
Page 42: ...Manual Corvus eco Starting up 42...
Page 43: ...Chapter 3 Manual Corvus eco Functions 43 Functions...
Page 67: ...Chapter 4 Manual Corvus eco Technical data 67 Technical data...
Page 70: ...Manual Corvus eco Technical data 70 Layout and dimensions...
Page 71: ...Chapter 5 Manual Corvus eco Releasing options 71 Releasing options...
Page 77: ...Manual Corvus Releasing options 77...
Page 80: ...Manual Corvus Releasing options 80...
Page 81: ...Chapter 6 Manual Corvus eco Firmware update 81 Firmware update...
Page 83: ...Manual Corvus Firmware update 83 Update Tool...
Page 84: ...Manual Corvus Firmware update 84...
Page 85: ...Chapter 7 Manual Corvus eco Connectors 85 Connectors...