Application Guide
P72x/EN AP/C21
MiCOM P721/P723
Page 3/52
1. INTRODUCTION
1.1
P72x High Impedance Differential Relay
The P72x relay, used with a stabilizing resistor, is designed for applications where sensitive
settings and stability on heavy through faults are required. It is recommended for balanced
and restricted earth fault schemes, bus-zone and certain forms of differential protection for
generators, auto-transformers, reactors and motors.
The sampling rate of the P72x is 32 samples per cycle. A Measurement Filter setting is
available in the P72x, so that the relay may operate in three different modes. The first one is
the Fourier mode, the relay is tuned to the supply frequency, and the harmonics and DC
component produced by current transformer saturation are filtered. The second option is
Sample mode. This mode is based on the peak to peak measurement of the differential
current. A fault is detected when
setting
2
2
I
peak
peak
diff
>
×
−
. Finally, the relay may be set to
Fast sample mode, and a fault is detected when
setting
2
2
I
eous
tan
tan
ins
diff
×
×
>
. In Fast
sample mode a trip is issued if four consecutive differential current samples are above
setting
2
2
×
×
in one half cycle.
1.2 Busbar
Protection
Busbar protection must be completely reliable since the protection may only be called to
operate once or twice in the life of the installation. Failure to operate under fault conditions is
unacceptable because the damage that results from an uncleared fault may be extensive, for
example, the loss of the station by fire. In addition, the protection must be high speed in
operation to minimize damage and maintain system stability. It must also be absolutely
stable under all through fault conditions because failure to stabilize would cause
unnecessary widespread interruption of supply.
If the busbar is subdivided into sections, each of which is separately protected, a fault in one
section does not involve the tripping of the complete busbar. Therefore, the protection must
discriminate between sections of the busbars so that the minimum number of circuit breakers
is tripped to isolate the fault.
The following are commonly used busbar protections:
•
Frame to earth (leakage) protection
•
Differential
protection
•
Directional comparison (blocking schemes) protection
The P72x relays operate on the high impedance principle. Therefore, the application of high
impedance busbar protection in different busbar arrangements is considered in the following
sections.
The high impedance differential scheme is simple and fast, but it requires good CT inputs
with well matched ratios and high CT kneepoints. At 5In the typical operating times when
the P72x is used in REF/BEF applications is 40 ms for Fourier, 34 ms for Fast and 52 ms for
Sample.
At 5In the typical operating times when the P72x is used in busbar applications is
18 ms for Fourier, 18 ms for Fast and 38 ms for Sample.
1.3 Reactor
Protection
To calculate the stability voltage when protecting a reactor with a high impedance scheme, it
should be noted that the external fault current contribution from the reactor is much smaller
than the internal fault current. Therefore, the reactor inrush current should be used in
stability calculations instead of the external fault current.
Summary of Contents for P721
Page 2: ......
Page 4: ...P72x EN T C21 Technical Guide Contents Page 2 2 MiCOM P721 P723 BLANK PAGE...
Page 5: ...Pxxx EN SS G11 SAFETY SECTION...
Page 6: ......
Page 8: ...Pxxx EN SS G11 Page 2 8 Safety Section BLANK PAGE...
Page 15: ...Introduction P72x EN IT C21 MiCOM P721 P723 INTRODUCTION...
Page 16: ......
Page 18: ...P72x EN IT C21 Introduction Page 2 10 MiCOM P721 P723 BLANK PAGE...
Page 26: ...P72x EN IT C21 Introduction Page 10 10 MiCOM P721 P723 BLANK PAGE...
Page 28: ......
Page 30: ...P72x EN IN C21 Handling Installation and Case Dimensions Page 2 10 MiCOM P721 P723 BLANK PAGE...
Page 39: ...User Guide P72x EN FT C21 MiCOM P721 P723 USER GUIDE...
Page 40: ......
Page 78: ...P72x EN FT C21 User Guide Page 38 38 MiCOM P721 P723 BLANK PAGE...
Page 79: ...Menu Content Tables P72x EN HI C21 MiCOM P721 P723 MENU CONTENT TABLES...
Page 80: ...P72x EN HI C21 Menu Content Tables MiCOM P721 P723 BLANK PAGE...
Page 82: ...P72x EN HI C21 Menu Content Tables Page 2 8 MiCOM P721 P723 BLANK PAGE...
Page 89: ...Technical Data P72x EN TD A11 MiCOM P721 P723 TECHNICAL DATA...
Page 90: ......
Page 108: ...P72x EN TD A11 Technical Data Page 18 18 MiCOM P721 P723 BLANK PAGE...
Page 109: ...Getting Started P72x EN GS C21 MiCOM P721 P723 GETTING STARTED...
Page 110: ......
Page 112: ...P72x EN GS C21 Getting Started Page 2 24 MiCOM P721 P723 BLANK PAGE...
Page 135: ...Application Guide P12x EN AP C21 MiCOM P721 P723 APPLICATION GUIDE...
Page 136: ......
Page 189: ...Communication database P72x EN CT A11 MiCOM P721 P723 COMMUNICATION DATABASE...
Page 190: ...P72x EN CT A11 Communication database MiCOM P721 P723 BLANK PAGE...
Page 192: ...P72x EN CT A11 Communication database Page 2 78 MiCOM P721 P723 BLANK PAGE...
Page 238: ...P72x EN CT A11 Communication database Page 48 78 MiCOM P721 P723 BLANK PAGE...
Page 240: ...P72x EN CT A11 Communication database Page 50 78 MiCOM P721 P723 BLANK PAGE...
Page 252: ...P72x EN CT A11 Communication database Page 62 78 MiCOM P721 P723 BLANK PAGE...
Page 254: ...P72x EN CT A11 Communication database Page 64 78 MiCOM P721 P723 BLANK PAGE...
Page 256: ...P72x EN CT A11 Communication database Page 66 78 MiCOM P721 P723 BLANK PAGE...
Page 268: ...P72x EN CT A11 Communication database Page 78 78 MiCOM P721 P723 BLANK PAGE...
Page 270: ......
Page 298: ...P72x EN CM C21 Commissioning and Maintenance Page 28 28 MiCOM P721 P723 BLANK PAGE...
Page 299: ...Connection Diagrams P72x EN CO A11 MiCOM P721 P723 CONNECTION DIAGRAMS...
Page 300: ......
Page 304: ......
Page 306: ...P72x EN RS A11 Commissioning Test Record Sheets Page 2 22 MiCOM P721 P723 BLANK PAGE...
Page 326: ...P72x EN RS A11 Commissioning Test Record Sheets Page 22 22 MiCOM P721 P723 BLANK PAGE...
Page 328: ......
Page 333: ......