P72x/EN CM/C21
Commissioning and Maintenance
Page 26/28
MiCOM P721/P723
Remove the screws used to fasten the relay to the panel, rack, etc.. These are the screws
with the larger diameter heads that are accessible when the upper and lower flaps are
installed.
Carefully withdraw the relay from the panel or rack because it will be heavy due to the
internal transformers.
To reinstall the repaired or replacement relay, follow the above instructions in reverse,
ensuring that each terminal block is relocated in the correct position and that the case earth
and communication are replaced.
Once reinstallation is complete the relay should be recommissioned.
5.3 Problem
solving
5.3.1
Password lost or not accepted
Problem:
Password lost or not accepted
Cause:
MiCOM P721
and
P723
relays are supplied with the password set to
AAAA.
This password can be changed by the user (refer OP PARAMETERS menu).
Action:
There is an additional unique recovery password associated with the relay which can be
supplied by the factory or service agent, if given details of its serial number (under the upper
flap of the front panel). With this serial number, contact your Schneider Electric local dealer
or Customer Contact Center (
http://www.schneider-electric.com/CCC
5.3.2 Communication
5.3.2.1
Values measured locally and remotely.
Problem:
The measurements noted remotely and locally (via RS485 communication) differ.
Cause:
The values accessible on the front face via the Measurement menu are refreshed every
second. Those fed back via RS485 communication and accessible by the Schneider
Electric’s Setting software generally have skeletal refreshing frequencies. If the refreshing
frequency of the supervision software differs from that of
MiCOM P721
and
P723
relays (1s),
there may be a difference between indicated values.
Action:
Adjust the frequency for refreshing the measurements of the supervision software or of the
setting software to 1 second.
5.3.2.2
MiCOM relay no longer responds
Problem:
No response from
MiCOM P721
and
P723
relays when asked by the supervision software
without any communication fault message.
Cause:
Mainly, this type of problem is linked to an error in the
MiCOM P721
and
P723
communication parameters.
Summary of Contents for P721
Page 2: ......
Page 4: ...P72x EN T C21 Technical Guide Contents Page 2 2 MiCOM P721 P723 BLANK PAGE...
Page 5: ...Pxxx EN SS G11 SAFETY SECTION...
Page 6: ......
Page 8: ...Pxxx EN SS G11 Page 2 8 Safety Section BLANK PAGE...
Page 15: ...Introduction P72x EN IT C21 MiCOM P721 P723 INTRODUCTION...
Page 16: ......
Page 18: ...P72x EN IT C21 Introduction Page 2 10 MiCOM P721 P723 BLANK PAGE...
Page 26: ...P72x EN IT C21 Introduction Page 10 10 MiCOM P721 P723 BLANK PAGE...
Page 28: ......
Page 30: ...P72x EN IN C21 Handling Installation and Case Dimensions Page 2 10 MiCOM P721 P723 BLANK PAGE...
Page 39: ...User Guide P72x EN FT C21 MiCOM P721 P723 USER GUIDE...
Page 40: ......
Page 78: ...P72x EN FT C21 User Guide Page 38 38 MiCOM P721 P723 BLANK PAGE...
Page 79: ...Menu Content Tables P72x EN HI C21 MiCOM P721 P723 MENU CONTENT TABLES...
Page 80: ...P72x EN HI C21 Menu Content Tables MiCOM P721 P723 BLANK PAGE...
Page 82: ...P72x EN HI C21 Menu Content Tables Page 2 8 MiCOM P721 P723 BLANK PAGE...
Page 89: ...Technical Data P72x EN TD A11 MiCOM P721 P723 TECHNICAL DATA...
Page 90: ......
Page 108: ...P72x EN TD A11 Technical Data Page 18 18 MiCOM P721 P723 BLANK PAGE...
Page 109: ...Getting Started P72x EN GS C21 MiCOM P721 P723 GETTING STARTED...
Page 110: ......
Page 112: ...P72x EN GS C21 Getting Started Page 2 24 MiCOM P721 P723 BLANK PAGE...
Page 135: ...Application Guide P12x EN AP C21 MiCOM P721 P723 APPLICATION GUIDE...
Page 136: ......
Page 189: ...Communication database P72x EN CT A11 MiCOM P721 P723 COMMUNICATION DATABASE...
Page 190: ...P72x EN CT A11 Communication database MiCOM P721 P723 BLANK PAGE...
Page 192: ...P72x EN CT A11 Communication database Page 2 78 MiCOM P721 P723 BLANK PAGE...
Page 238: ...P72x EN CT A11 Communication database Page 48 78 MiCOM P721 P723 BLANK PAGE...
Page 240: ...P72x EN CT A11 Communication database Page 50 78 MiCOM P721 P723 BLANK PAGE...
Page 252: ...P72x EN CT A11 Communication database Page 62 78 MiCOM P721 P723 BLANK PAGE...
Page 254: ...P72x EN CT A11 Communication database Page 64 78 MiCOM P721 P723 BLANK PAGE...
Page 256: ...P72x EN CT A11 Communication database Page 66 78 MiCOM P721 P723 BLANK PAGE...
Page 268: ...P72x EN CT A11 Communication database Page 78 78 MiCOM P721 P723 BLANK PAGE...
Page 270: ......
Page 298: ...P72x EN CM C21 Commissioning and Maintenance Page 28 28 MiCOM P721 P723 BLANK PAGE...
Page 299: ...Connection Diagrams P72x EN CO A11 MiCOM P721 P723 CONNECTION DIAGRAMS...
Page 300: ......
Page 304: ......
Page 306: ...P72x EN RS A11 Commissioning Test Record Sheets Page 2 22 MiCOM P721 P723 BLANK PAGE...
Page 326: ...P72x EN RS A11 Commissioning Test Record Sheets Page 22 22 MiCOM P721 P723 BLANK PAGE...
Page 328: ......
Page 333: ......