Commissioning and Maintenance
P72x/EN CM/C21
MiCOM P721/P723
Page 25/28
5.1.3
Hardware and software faults
Messages:
"DEFAULT SETTING": Indication that the relay is running the default setting
"SETTING ERROR": Failure in the setting
" CALIBRATION ERROR.": Calibration zone failure
"CT ERROR": Analogue channel failure
Cause:
Hardware or software failure
Action:
Restart the protection software (refer § 5.3).
If the software fault still remains after restart, withdraw the active part and return the module
to the factory for repair.
5.2
Method of repair
5.2.1
Replacing the active part
BEFORE CARRYING OUT ANY WORK ON THE EQUIPMENT, THE
USER SHOULD BE FAMILIAR WITH THE CONTENTS OF THE SAFETY
GUIDE SFTY/4LM/E11 OR LATER ISSUE, OR THE SAFETY AND
TECHNICAL DATA SECTIONS OF THE TECHNICAL MANUAL AND
ALSO THE RATINGS ON THE EQUIPMENT RATING LABEL.
The case and the rear terminals blocks have been designed to facilitate removal of the
MiCOM P72x relay should replacement or repair become necessary without disconnect the
scheme wiring.
NOTE:
The MiCOM range of relays have integral current transformer shorting
switches which will close when the active part is removed from the
case.
Remove the upper and lower flap without exerting excessive force. Remove the external
screws. Under the upper flap, turn the extractor with a 3 mm screwdriver and extract the
active part of the relay by pulling from the upper and lower notches on the front panel of the
MiCOM relay.
To reinstall the repaired or replacement relay follow the above instructions in reverse,
ensuring that no modification has been made to the scheme wiring.
On completion of any operations which require the relay to be removed from its case, verify
that the four fixing screws are fitted at the corners of the front panel under the flaps. These
screws secure the chassis (removable part) to the relay case, ensuring good seating and
contact.
5.2.2
Replacing the complete relay
To remove the complete relay (active part and case) the entire wiring must be removed from
the rear connector.
Before working at the rear of the relay, isolate all current supplies to the MiCOM relay and
ensure that the relay is no longer powered.
WARNING: NEVER
OPEN THE SECONDARY CIRCUIT OF A CURRENT
TRANSFORMER SINCE THE HIGH VOLTAGE PRODUCED MAY BE
LETHAL AND COULD DAMAGE THE INSULATION.
Remove all wiring (communication, logic inputs, outputs, auxiliary voltage, current inputs).
Disconnect the relay earth connection from the rear of the relay.
Summary of Contents for P721
Page 2: ......
Page 4: ...P72x EN T C21 Technical Guide Contents Page 2 2 MiCOM P721 P723 BLANK PAGE...
Page 5: ...Pxxx EN SS G11 SAFETY SECTION...
Page 6: ......
Page 8: ...Pxxx EN SS G11 Page 2 8 Safety Section BLANK PAGE...
Page 15: ...Introduction P72x EN IT C21 MiCOM P721 P723 INTRODUCTION...
Page 16: ......
Page 18: ...P72x EN IT C21 Introduction Page 2 10 MiCOM P721 P723 BLANK PAGE...
Page 26: ...P72x EN IT C21 Introduction Page 10 10 MiCOM P721 P723 BLANK PAGE...
Page 28: ......
Page 30: ...P72x EN IN C21 Handling Installation and Case Dimensions Page 2 10 MiCOM P721 P723 BLANK PAGE...
Page 39: ...User Guide P72x EN FT C21 MiCOM P721 P723 USER GUIDE...
Page 40: ......
Page 78: ...P72x EN FT C21 User Guide Page 38 38 MiCOM P721 P723 BLANK PAGE...
Page 79: ...Menu Content Tables P72x EN HI C21 MiCOM P721 P723 MENU CONTENT TABLES...
Page 80: ...P72x EN HI C21 Menu Content Tables MiCOM P721 P723 BLANK PAGE...
Page 82: ...P72x EN HI C21 Menu Content Tables Page 2 8 MiCOM P721 P723 BLANK PAGE...
Page 89: ...Technical Data P72x EN TD A11 MiCOM P721 P723 TECHNICAL DATA...
Page 90: ......
Page 108: ...P72x EN TD A11 Technical Data Page 18 18 MiCOM P721 P723 BLANK PAGE...
Page 109: ...Getting Started P72x EN GS C21 MiCOM P721 P723 GETTING STARTED...
Page 110: ......
Page 112: ...P72x EN GS C21 Getting Started Page 2 24 MiCOM P721 P723 BLANK PAGE...
Page 135: ...Application Guide P12x EN AP C21 MiCOM P721 P723 APPLICATION GUIDE...
Page 136: ......
Page 189: ...Communication database P72x EN CT A11 MiCOM P721 P723 COMMUNICATION DATABASE...
Page 190: ...P72x EN CT A11 Communication database MiCOM P721 P723 BLANK PAGE...
Page 192: ...P72x EN CT A11 Communication database Page 2 78 MiCOM P721 P723 BLANK PAGE...
Page 238: ...P72x EN CT A11 Communication database Page 48 78 MiCOM P721 P723 BLANK PAGE...
Page 240: ...P72x EN CT A11 Communication database Page 50 78 MiCOM P721 P723 BLANK PAGE...
Page 252: ...P72x EN CT A11 Communication database Page 62 78 MiCOM P721 P723 BLANK PAGE...
Page 254: ...P72x EN CT A11 Communication database Page 64 78 MiCOM P721 P723 BLANK PAGE...
Page 256: ...P72x EN CT A11 Communication database Page 66 78 MiCOM P721 P723 BLANK PAGE...
Page 268: ...P72x EN CT A11 Communication database Page 78 78 MiCOM P721 P723 BLANK PAGE...
Page 270: ......
Page 298: ...P72x EN CM C21 Commissioning and Maintenance Page 28 28 MiCOM P721 P723 BLANK PAGE...
Page 299: ...Connection Diagrams P72x EN CO A11 MiCOM P721 P723 CONNECTION DIAGRAMS...
Page 300: ......
Page 304: ......
Page 306: ...P72x EN RS A11 Commissioning Test Record Sheets Page 2 22 MiCOM P721 P723 BLANK PAGE...
Page 326: ...P72x EN RS A11 Commissioning Test Record Sheets Page 22 22 MiCOM P721 P723 BLANK PAGE...
Page 328: ......
Page 333: ......