Application Guide
P72x/EN AP/C21
MiCOM P721/P723
Page 47/52
6. MAINTENANCE
MODE
This menu allows the user to verify the operation of the protection functions without actually
sending any external command (Tripping or signaling).
The maintenance mode can be selected using a logic input, control command (rear or front
port), or by front panel interface. The end of maintenance mode is done by logic input, by
control command or on the front panel interface time out (5 minutes) and by turning off the
power supply.
Maintenance Mode
YES
When this menu is activated (set to YES), the Alarm LED flashes and the alarm message
MAINTENANCE MODE
appears on the display. In this case, all the output contacts are
blocked and no command can be issued to these contacts, even if a protection threshold
associated to one of these output contacts has been crossed.
(If a protection threshold is crossed, all associated LEDs will be ON, even the TRIP LED, if
the threshold is associated to RL1).
RELAYS 8765W4321
CMD 000000000
This window allows the user to verify the external wiring to the relay output contacts. To do
this, the user must assign a 1 to any of the output contacts, which will close the contact, and
the continuity of the wiring can be verified.
7.
LOGIC EQUATIONS (P721 & P723)
The logic equations can be used to construct complex Boolean logic using the following
operators: AND NOT, OR NOT, AND, OR.
An example logic implementation using Equation A is shown below:
8.
REAL TIME CLOCK SYNCHRONIZATION VIA OPTO-INPUTS
In modern protective schemes it is often desirable to synchronize the relay’s real time clock
so that events from different relays can be placed in chronological order. This can be done
using the communication interface connected to the substation control system or through an
opto-input. Any of the available opto-inputs on the P72x relay can be selected for
synchronization. Pulsing this input results in the real time clock snapping to the nearest
minute. The recommended pulse duration is 20 ms, to be repeated no more than once per
minute.
The following table shows an example of the time synchronization function and assumes a
time format of hh:mm:ss.
Time of “Sync. Pulse”
Corrected Time
19:47:00.000 to 19:47:29.999
19:47:00.000
19:47:30.000 to 19:47:59.999
19:48:00.000
Summary of Contents for P721
Page 2: ......
Page 4: ...P72x EN T C21 Technical Guide Contents Page 2 2 MiCOM P721 P723 BLANK PAGE...
Page 5: ...Pxxx EN SS G11 SAFETY SECTION...
Page 6: ......
Page 8: ...Pxxx EN SS G11 Page 2 8 Safety Section BLANK PAGE...
Page 15: ...Introduction P72x EN IT C21 MiCOM P721 P723 INTRODUCTION...
Page 16: ......
Page 18: ...P72x EN IT C21 Introduction Page 2 10 MiCOM P721 P723 BLANK PAGE...
Page 26: ...P72x EN IT C21 Introduction Page 10 10 MiCOM P721 P723 BLANK PAGE...
Page 28: ......
Page 30: ...P72x EN IN C21 Handling Installation and Case Dimensions Page 2 10 MiCOM P721 P723 BLANK PAGE...
Page 39: ...User Guide P72x EN FT C21 MiCOM P721 P723 USER GUIDE...
Page 40: ......
Page 78: ...P72x EN FT C21 User Guide Page 38 38 MiCOM P721 P723 BLANK PAGE...
Page 79: ...Menu Content Tables P72x EN HI C21 MiCOM P721 P723 MENU CONTENT TABLES...
Page 80: ...P72x EN HI C21 Menu Content Tables MiCOM P721 P723 BLANK PAGE...
Page 82: ...P72x EN HI C21 Menu Content Tables Page 2 8 MiCOM P721 P723 BLANK PAGE...
Page 89: ...Technical Data P72x EN TD A11 MiCOM P721 P723 TECHNICAL DATA...
Page 90: ......
Page 108: ...P72x EN TD A11 Technical Data Page 18 18 MiCOM P721 P723 BLANK PAGE...
Page 109: ...Getting Started P72x EN GS C21 MiCOM P721 P723 GETTING STARTED...
Page 110: ......
Page 112: ...P72x EN GS C21 Getting Started Page 2 24 MiCOM P721 P723 BLANK PAGE...
Page 135: ...Application Guide P12x EN AP C21 MiCOM P721 P723 APPLICATION GUIDE...
Page 136: ......
Page 189: ...Communication database P72x EN CT A11 MiCOM P721 P723 COMMUNICATION DATABASE...
Page 190: ...P72x EN CT A11 Communication database MiCOM P721 P723 BLANK PAGE...
Page 192: ...P72x EN CT A11 Communication database Page 2 78 MiCOM P721 P723 BLANK PAGE...
Page 238: ...P72x EN CT A11 Communication database Page 48 78 MiCOM P721 P723 BLANK PAGE...
Page 240: ...P72x EN CT A11 Communication database Page 50 78 MiCOM P721 P723 BLANK PAGE...
Page 252: ...P72x EN CT A11 Communication database Page 62 78 MiCOM P721 P723 BLANK PAGE...
Page 254: ...P72x EN CT A11 Communication database Page 64 78 MiCOM P721 P723 BLANK PAGE...
Page 256: ...P72x EN CT A11 Communication database Page 66 78 MiCOM P721 P723 BLANK PAGE...
Page 268: ...P72x EN CT A11 Communication database Page 78 78 MiCOM P721 P723 BLANK PAGE...
Page 270: ......
Page 298: ...P72x EN CM C21 Commissioning and Maintenance Page 28 28 MiCOM P721 P723 BLANK PAGE...
Page 299: ...Connection Diagrams P72x EN CO A11 MiCOM P721 P723 CONNECTION DIAGRAMS...
Page 300: ......
Page 304: ......
Page 306: ...P72x EN RS A11 Commissioning Test Record Sheets Page 2 22 MiCOM P721 P723 BLANK PAGE...
Page 326: ...P72x EN RS A11 Commissioning Test Record Sheets Page 22 22 MiCOM P721 P723 BLANK PAGE...
Page 328: ......
Page 333: ......