5-4-2 Application Code setting group 1 (d codes) table
This group contains setting parameters, which are either ON or OFF.
NEW
– Function Added
Memorizing Application Code Settings
– Application Code Setting can be retained after any control box reset.
(Previously, application code settings were also returned to default settings after a control box reset.)
See Application Code ‘dP’ to retain Applications Code Settings.
CODE
INDICATION
Parameter name
DESCRIPTION
LED 4 (RED)
LED 1 LED 2
ON
OFF*
d
0
BUZZER
Set ON when you need buzzer sound, in case of error,
battery operation or PS operation.
ON
OFF
d
1
CLOSE BRAKING
POSITION
Set ON (150mm) if you need a wider cushion / low
speed travel range before fully closed.
150mm 70mm
d
2*
18 / 30 MODE
(AUTO)
Setting Automatically when the motor for EDM30NII is
connected.
30
18
d
3
ELECTROMAGNETIC
LOCK
Setting ON Automatically if an Electromagnetic Lock is
detected. Set to OFF when the Electromagnetic Lock is
NOT connected.
YES
NO
d
4
BATTERY SYSTEM
(Emergency system)
Set on with Battery Close system (BC) or
Set on when you need to CLOSE by Panic Signal (PS).
BC
BO
d
5
OPEN PRESSING
Set ON if you do not need pressing force at full open.
NO
YES
d
6*
CLOSE PRESSING
(Vibration detected)
Set ON if the motor generates vibration at closed
position.
Closing press will be cut off only when vibration
detected.
Set OFF. Always closing press at full close.
YES &
NO
YES
d
7
HALF OPEN mode
(Partial open)
Set ON if you do NOT wish partial open to go to full
open automatically.
FIX
AUTO
d
8
RS
– Hold Open
Ratchet Switch
New Function - If SB is ON during closing, the door will
re-open and remain open in Ratchet (RS). To close,
switch (RS) must be activated again. Set ON to Hold
Open after SB.
ON
OFF
d
9
SB FUNCTION ON
CLOSE END
Set on if you need to open by SB signal when the door
fully closed.
YES
NO
d
A
SELF CLOSING
DEVICE
(Mechanical open
device)
Set ON if mechanical self closing device is fitted (Japan
Only)
YES
NO