5-4-3 Application code setting group 2 (P codes) table
Note: Setting P1 to Pd & PF are for Japanese domestic use and not required to be employed out side
of Japan. The full range of P codes are available, however only PE code is only NECESSARY to be
utilized when required.
We recommend NOT changing these parameters unless advised to do so. They are for special use,
except in the case of PE code, which changes Normal Open Contacts to Normal Close Contacts.
CODE INDICATION
Description
CODE
SETTING
P1
00~60
Error detection threshold during high speed opening cycle
P2
00~60
Error detection threshold during low speed opening cycle
P3
00~50
Low speed travel range during opening cycle.
P4
0.3~2.5
Start opening error detection time
P5
00~50
Error detection threshold during high speed closing cycle
P6
00~10
Error detection threshold during low speed closing cycle
P7
00~50
Low speed travel range during closing cycle.
P8
0.3~2.5
Start closing error detection time
Pb
0.0~1.0
Door opening delay time
PC
02~30
Activation signal delay time
Pd
00~50
Error detection threshold by obstacle size during closing cycle
PE
00~0F
NO, NC SELECTION (SEE CHART BELOW)
PF
00~09
Before closing warning signal time
PH
00-05
Breaking & Stop Movement
– Time before Low Speed after breaking
PJ
02-04
Interval of Door Speed Checking (02=0.2sec / 04=0.4sec)
Setting PH-00 & PJ-02
– Door movement from breaking to low speed is very
smooth
Setting PH-05 & PJ-04 - Door movement from breaking to low speed is very
sudden. (Door Stop
– Low Speed)
PL
00--02
Open Pressing Power
If you change from default setting the parameter of P code, the RED LED is turned to ON.