MD 9273 Leakage Clamp
Technical Specifications
24
TRMS current/voltage value
Function
Range
Resolution
Accuracy
mA,
A
40 mA
0.01 mA
± 0.8 % of reading ± 3 digits
400 mA
0.1 mA
± 0.8 % of reading ± 3 digits
4 A
0.001 A
± 0.8 % of reading ± 3 digits
40 A
0.01 A
± 1 % of reading ± 3
digits
80 A
0.1 A
± 1.2 % of reading ± 3 digits
100 A
0.1 A
± 5 % of reading
V
40 V
0.01 V
± 0.5 % of reading ± 4 digits
400 V
0.1 V
± 0.5 % of reading ± 2 digits
600 V
1 V
± 0.5 % of reading ± 2 digits
THD
0 … 99.9 %
0.1 %
± 2 % of reading ± 3 digits
100
… 999 %
1 %
± 2 % of reading ± 3 digits
Note: the specifications are valid for waveforms with fundamental frequency between 45 Hz and 70 Hz and
crest factor < 3.
DC voltage
V
40 V
0.01 V
± 0.5 % of reading ± 4 digits
400 V
0.1 V
± 0.5 % of reading ± 2 digits
600 V
1 V
± 0.5 % of reading ± 2 digits
Frequency
Hz
10 - 500 Hz
0.1 Hz
± 0.
1
% ±
2 digits
Note: The instrument is designed to measure power supply voltage and current signals in the range of 45
–
70 Hz and observes them as first harmonic. If the measured signal has frequency is greater than 70 Hz, the
instrument will understand it as a higher harmonic.
Note: Frequency is measured at voltages higher than 15% of range or 0.3 V (whichever is higher). Manually
change range to lower one if the instrument doesn’t
display the frequency while the signal is higher than 0.3
V.