Installation manual
M-WRG-S/Z-S, M-WRG-S/Z-24,
M-WRG-S/Z-EIB, M-WRG-S/Z-KNX (-F, -FC)
- 22 -
Meltem Wärmerückgewinnung GmbH & Co. KG
Am Hartholz 4 · D-82239 Alling
[email protected] · www.meltem.com
VENTILATION THE RIGHT WAY
V E N T I L AT I O N & H E AT R E C O V E R Y
NOTE
—
The DIP switches and jumpers on the board are preset at the factory.
►
Do not change the position of any DIP switches or jumpers.
—
The KNX interface ABB US/U 12.2 was connected to the terminal blocks on the board at
the factory.
—
You will find the terminal assignment for the ventilation unit in Table 11, Table 12 or Ta
ble 13 in section 9.3 from page 23.
9.1.3 Position of the assemblies
Fig. 16: KNX interface
1
1
2
3
Fig. 17: KNX interface and board with terminal blocks
Item Designation
1
KNX interface ABB US/U 12.2
Item Designation
1
KNX interface ABB US/U 12.2
2
Opening for KNX bus cable
3
Network connection cover
9.2
Control cable types (KNX bus cable)
Part no.
Type of ventilation unit Control cable types (KNX bus cable)
5016-1-2
5016-1-2-1
5016-1-2-2
M-WRG-S/Z-KNX
M-WRG-S/Z-KNX-F
M-WRG-S/Z-KNX-FC
J-Y (St) Y 2 x 2 x 0.8 mm
2
or EIB-Y (St) Y 2 x 2 x 0.8 mm
2
Table 10: Allocation of ventilation unit type and control cable type (KNX bus cable)