9.3
Terminal assignment of the KNX interface
9.3.1 M-WRG-S/Z-KNX ventilation unit
Terminal on
board
KNX interface ABB US/U 12.2
Function
Terminal
designation
Wire colour
1
0V
BK
2
GY
3
A
BN
Reduced ventilation
4
B
RD
Normal ventilation
5
C
OG
Increased ventilation
6
D
YE
Intensive ventilation
7
E
BN
Reduced ventilation LED
8
F
RD
Normal ventilation LED
9
G
OG
Increased ventilation LED
10
H
YE
Intensive ventilation LED
11
I
BN
Supply air operation
12
J
RD
Extract air operation
13
14
15
K
OG
Supply air operation LED
16
L
YE
Exhaust air operation LED
17
18
Table 11: Terminal assignment of KNX interface for M-WRG-S/Z-KNX ventilation unit
9.3.2 M-WRG-S/Z-KNX-F ventilation unit
Terminal on
board
KNX interface ABB US/U 12.2
Function
Terminal
designation
Wire colour
1
0V
BK
2
GY
3
A
BN
Reduced ventilation
4
B
RD
Normal ventilation
5
C
OG
Increased ventilation
6
D
YE
Intensive ventilation
7
E
BN
Reduced ventilation LED
8
F
RD
Normal ventilation LED
9
G
OG
Increased ventilation LED