Installation manual
M-WRG-S/Z-S, M-WRG-S/Z-24,
M-WRG-S/Z-EIB, M-WRG-S/Z-KNX (-F, -FC)
- 11 -
Meltem Wärmerückgewinnung GmbH & Co. KG
Am Hartholz 4 · D-82239 Alling
[email protected] · www.meltem.com
VENTILATION THE RIGHT WAY
V E N T I L AT I O N & H E AT R E C O V E R Y
6.3.3.2 Circuit diagram
Fig. 4: Circuit diagram for wiring the M-WRG-S/Z-S ventilation unit with control cable and optional pushbutton/LED
+
24
VDC
0
V
+24 VDC
+24 VDC
0 V
1
5
3
2
01 02 03 04 05 06 07 08 09 10
03
01 02
10
04 05 06 07 08 09
Board in M-WRG-S/Z-S ventilation unit,
ventilation unit 1
Board in M-WRG-S/Z-S ventilation unit,
ventilation unit 2 (max. 5 ventilation units)
Three-step rotary switch with
zero position,
BUSCH-JAEGER 2710 U
Optional: pushbutton and LED for intensive
ventilation
Optional: LED for
intensive ventilation
NOTE
Connect terminal 02 (+24 VDC) to one
ventilation unit only.
NOTE
Feedback signals cannot
be switched together to
create a single group
signal.
Ventilation level I
Ventilation level II
Ventilation level III
Intensive ventilation
NOTE
—
Up to five M-WRG-S/Z-S ventilation units may be connected to the three-step rotary switch
and intensive ventilation pushbutton. No separate power supply is needed.
—
Please note the following if you intend to connect more than one M-WRG-S/Z-S ventilation
unit to the three-step rotary switch:
— The terminals 01 (0 V) of all ventilation units must be connected to one another (see
— The terminal 02 (+24 V DC) of the three-step rotary switch may only be connected to
the terminal 02 of a single ventilation unit (see Fig. 4).
—
The feedback from multiple ventilation units for intensive ventilation cannot be combined in
a single group signal.
—
The total length of the control cable must not exceed 50 m.