8.3.2.4 Circuit diagram for wiring with feedback
Fig. 11: Circuit diagram for wiring the M-WRG-S/Z-EIB ventilation unit with feedback
A2
comm LEDs K
comm Schalter (+)
6119/40
03
01 02
10
04 05 06 07 08 09
A1
BCD IN E2
BCD IN E3
BCD IN E4
6
D
5
C
4
B
3
A
2
+
1
-
YE
OG
RD
BN
GY
BK
-
GY
+
RD
0 V
+5 VDC
Board in M-WRG-S/Z-EIB ventilation unit
EIB universal inter-
face with four inputs/
outputs
Terminals for
control cable
(EIB bus cable)
NOTE
—
With this wiring, signal A1 from terminal 7 on the board in the ventilation unit is connected
to terminal A on the EIB universal interface 6119/40. Terminal A is configured as an input.
The consequence of this is that only those functions in which terminal A is interpreted as
open can be activated. In this case, this would be the functions with BCD code 0, 2, 4, 6,
8, A, C, E (see BCD encoding in section 8.3.2.1 on page 17).
—
Note which functions are available if the feedback is wired at a terminal other than termi-
nal A.