Settings
47
5.2
Operating mode settings
Depending on the sensor connected, the settings menu
provides different submenus
for configuring the operating modes currently available. Depending on the
menu/operating mode, the following parameters can be specified:
Parameter
Menu/
Operating mode
Description
Frequency
Frequency at which the acoustic
measurement is performed
(
30 kHz
,
40 kHz
or
80 kHz
)
Volume
Headphone volume between 1–
100%
TEV LEVEL default
Selection of the sensor for which
the measured values should be
shown by default when making a
comparative measurement
(
internal
|
external
)
Number of steps
Number of measurement points
for a TEV measurement
sequence (
2
or
3
)
1st position
,
2nd position
,
3rd position
Order of the measurement points
at the substation during a TEV
measurement sequence (
top
,
middle
,
bottom
)
Diagram – Histogram
Activates/deactivates the
histogram screen in the
respective operating mode
Diagram – Pulse per
cycle
Activates/deactivates the pulse-
per-cycle screen in the
respective operating mode
Diagram – PRPD
Activates/deactivates the PRPD
screen in the respective
operating mode
Camera
Activates/deactivates the camera
function in the respective
operating mode (
On
,
Off
,
Marker
).
If set to
Marker
, a green cross is
displayed on the camera screen
as well. This cross is saved in
the image file.